Function of the Digital Input
Select one of the following functions for the digital input:
• Input
• Hardware gate
• Latch Function
• Synchronization
Function of the Digital Outputs
Select one of the following functions for each digital output:
• Output, no switching through comparator
• Activation at a counter status greater than or equal to the comparison value
• Activation at a counter status less than or equal to the comparison value
• Pulse on reaching the comparison value
• Switching at comparison values (DO1 only)
Influencing the Behavior of the Digital Outputs through:
The behavior of the digital outputs can be influenced as follows:
• Hysteresis
• Pulse duration
Changing values during operation
The following values can be changed during operation:
• Load value (LOAD_PREPARE)
• Counter status (LOAD_VAL)
• Comparison value 1 (CMP_VAL1)
• Comparison value 2 (CMP_VAL2)
• Function and behavior of the digital outputs (C_DOPARAM)
See also
Gate Functions in Count Modes (Page 135)
Latch Function (Page 137)
Synchronization (Page 140)
Behavior of the Outputs in Count Modes (Page 144)
Assignment of the Feedback and Control Interface for the Count Modes (Page 152)
Technological Functions