4.3 Example: Starting 1SSI
Configuring with STEP 7 using HW Config
You must first adapt the hardware configuration of your existing ET 200S station.
1. Open the relevant project in SIMATIC Manager.
2. Open the HW Config configuration table in your project.
3. From the hardware catalog, select the 1SSI entry with the number
4. Double-click this number to open the
5. Save and compile your configuration, and download the configuration in STOP mode of
224
6ES7 138-4DB03-0AB0 in the infotext. Drag the entry to the slot at which you have
installed your 1SSI.
Addresses
On the
tab, you will find the addresses of the slot to which you have dragged
the 1SSI. Make a note of these addresses for subsequent programming.
Parameters
On the
tab, you will find the default settings for the 1SSI. Select the encoder
type in accordance with the connected SSI encoder and enter all the required data. You
will find the encoder data on the type label and in the technical specifications of the
encoder.
the CPU by choosing "PLC > Download to Module".
DP Slave Properties
dialog box.