Assigning Parameters For Position Feedback - Siemens SIMATIC ET 200S Operating Instructions Manual

Technological functions
Hide thumbs Also See for SIMATIC ET 200S:
Table of Contents

Advertisement

3.8.7

Assigning Parameters for Position Feedback

Introduction
You can use either of the following to assign parameters for the 1Count5V/500kHz:
• A GSD file (http://www.ad.siemens.de/csi/gsd)
• STEP 7 V5.3 SP2 or later
Parameter list for Position Feedback
Table 3-27
Parameter list for Position Feedback
Parameter
Enable
Group diagnostics
Behavior in the event of the parent controller failing
Behavior at CPU/Master-STOP
Encoder parameters
Diagnostics A and B
Diagnostics N
Signal evaluation A, B
Direction input B
Mode
Position feedback
Gate function
Input signal HW gate
Function DI
Synchronization
1
Only relevant if Function DI = Synchronization on positive edge
1
Parameter Assignment Error
• The "Input signal HW gate" parameter is set to inverted and the "Function DI" parameter
What to Do in the Event of Errors
Check the set value ranges.
Technological Functions
Operating Instructions, 02/2007, A5E00124867-05
Value Range
Disable/enable
Turn off
Continue working mode
Off/on
Off/on
Pulse and direction/
Rotary encoder single/double/quadruple
Normal/Inverted
Position detection
Cancel counting/
Interrupt counting
Normal/Inverted
Input/
HW gate/
Latch and retrigger on positive edge/
Synchronization on positive edge
Once only/Periodic
is not set to HW gate.
1Count5V/500kHz
3.8 Position feedback
Default
Disable
Turn off
Off
Off
Pulse and direction
Normal
Position detection
Cancel counting
Normal
Input
Once-only
211

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents