General Technical Specifications
Data for the Digital Outputs
Output voltage
Output current
Minimum pulse duration
Accuracy
Output delay (with resistive load)
Lamp load
Control of a digital input
Switching frequency
Limitation (internal) of the inductive circuit
interruption voltage
Short-circuit protection for output
Cable lengths
Status, Interrupts, Diagnostics
Status indicators
Diagnostic functions
Update rate for feedback messages
Polarity reversal can lead to the digital outputs being switched through.
1
See the figures below
2
With a load of ≤ 50 Ω
3
Technological Functions
Operating Instructions, 02/2007, A5E00124867-05
With signal "1"
With signal "1"
Rated value
Permitted Range
With signal "0" (leakage current)
At "0" to "1"
At "1" to "0"
With resistive load
With inductive load
With lamp load
Response threshold
Unshielded
Shielded
Group error
Diagnostic information readable
5.5 Technical Specifications of the 2PULSE, Terminal Assignment
Minimum L+ - 1 V
2 A
7 mA...2 A
max. 0.5 mA
200 µs
± (pulse duration x 100 ppm) ±100 µs
max. 100 µs
max. 200 µs
Maximum 10 W
Yes
2.5 kHz
≤2 Hz
≤10 Hz
L+ -(50 V ... 65 V)
Yes
Typically 10 A
600 m
1000 m
Green LED for DI 0, DI 1, DO 0, DO 1
Red LED "SF"
Yes
1.2 ms
2)
2PULSE
3)
311