Siemens SIMATIC ET 200S Operating Instructions Manual page 288

Technological functions
Hide thumbs Also See for SIMATIC ET 200S:
Table of Contents

Advertisement

2PULSE
5.3 Modes and Functions
Parameters
Parameter
Group diagnostics
Diagnostics DO
Feedback Signals
Feedback Signals
ERR_PARA
ERR_PULS
ERR_24V
ERR_DO
288
Meaning
When group diagnostics has
been enabled, the 2PULSE
generates a diagnostic
message for the
CPU/master.
The 2PULSE detects a short
circuit of the digital output
DO when Diagnostics
DO=on.
Meaning
Indicates a parameter
assignment error.
Indicates a pulse output error.
Indicates a short circuit of the
encoder supply.
Indicates a short circuit of the
digital output DO. To do this, you
must enable Diagnostics DO.
Value Range
Disable/enable
Off/on
Value Range
0 = no parameter assignment
error
1 = parameter assignment error
0 = no pulse output error
1 = pulse output error
0 = no encoder supply short
circuit
1 = encoder supply short circuit
0 = no digital output short circuit
1 = digital output short circuit
Operating Instructions, 02/2007, A5E00124867-05
Default
Disable
Off
Channel 0
Channel 1
address
address
Byte 0:
Byte 4:
Bit 5
Bit 5
Byte 0:
Byte 4:
Bit 4
Bit 4
Byte 0:
Byte 4:
Bit 7
Bit 7
Byte 0:
Byte 4:
Bit 6
Bit 6