Parameter Assignment For Measurement Modes; Table 2-22 Parameter List For Measuring Modes - Siemens SIMATIC ET 200S Operating Instructions Manual

Technological functions
Hide thumbs Also See for SIMATIC ET 200S:
Table of Contents

Advertisement

1Count24V/100kHz
2.7 Measurement Modes
2.7.12

Parameter Assignment for Measurement Modes

Introduction
You can use either of the following to assign parameters for the 1Count24V/100kHz:
• A GSD file (http://www.ad.siemens.de/csi/gsd)
• STEP 7 V5.3 SP2 or later
Parameter List for Measuring Modes
Table 2-22
Parameter List for Measuring Modes
Parameter
Enable
Group diagnostics
Behavior in the event of the parent controller failing
Behavior at CPU/Master-STOP
Encoder parameters
Signal evaluation A, B
Encoder and input filter
- At count input (track A)
- At direction input (track B)
- At digital input DI
Sensor A, B, DI
Direction input B
Output parameters
Diagnostics DO1
1
Function DO1
Substitute value DO1
Mode
Measuring mode
Measuring method
Resolution of period
Function DI
Input signal HW gate
84
Value Range
Disable/enable
Turn off DO1/
Continue working mode/
DO1 substitute a value/
DO1 keep last value
Pulse and direction/
Rotary encoder (single)
2.5 µs/25 µs
2.5 µs/25 µs
2.5 µs/25 µs
24V P switch, normal mode/
24V M switch
Normal/Inverted
Off/on
Output/
Outside the limits/
Under the low limit/
Over the high limit
0/1
Frequency measurement/
Rotational speed measurement/
Period measurement
With integration time/continuous
1 µs
1/16 µs
Input/HW gate
Normal/Inverted
Default
Disable
Turn off DO1
Pulse and Direction
2.5 µs
2.5 µs
2.5 µs
24V P switch, normal mode
Normal
Off
Output
0
Frequency measurement
With integration time
1 µs
Input
Normal