INVT GD200-037G/045P-4 Operation Manual page 161

Goodrive200 series
Table of Contents

Advertisement

Goodrive200 inverters
Basic operation instruction
Function
Detailed instruction of parameters
Default
Name
code
value
(S1~S8,HDI) function
setting(DOWN)
selection
12:Cancel the frequency change setting
13:Shift between A setting and B setting
14:Shift between combination setting
and A setting
15:Shift between combination setting
and B setting
0x000~0x1223
LED ones:frequency enable selection
0:Both ∧/∨ keys and digital
potentiometer adjustments are valid
1:Only ∧/∨ keys adjustment is valid
2:Only digital potentiometer adjustments
is valid
3:Neither ∧/∨ keys nor digital
potentiometer adjustments are valid
LED tens: frequency control selection
0:Only valid when P00.06=0 or P00.07=0
1:Valid for all frequency setting manner
P08.42
Keypad data control
2:Invalid for multi-step speed when
0x0000
multi-step speed has the priority
LED hundreds: action selection during
stopping
0:Setting is valid
1:Valid during running, cleared after
stopping
2:Valid during running, cleared after
receiving the stop command
LED thousands: ∧/∨ keys and digital
potentiometer integral function
0:The integral function is valid
1:The integral function is invalid