Goodrive200 inverters
Function
Name
code
Keypad
P08.42
data
control
Integral
ratio of the
P08.43
keypad
potentiome
ter
UP/DOWN
P08.44
terminals
control
Detailed instruction of parameters
1: Heavy overcommission
0x000~0x1223
LED ones:frequency enable selection
0:Both ∧/∨ keys and digital potentiometer
adjustments are valid
1:Only ∧/∨ keys adjustment is valid
2:Only digital potentiometer adjustments is valid
3:Neither ∧/∨ keys nor digital potentiometer
adjustments are valid
LED tens: frequency control selection
0:Only valid when P00.06=0 or P00.07=0
1:Valid for all frequency setting manner
2:Invalid for multi-step speed when multi-step
speed has the priority
LED hundreds: action selection during stopping
0:Setting is valid
1:Valid during running, cleared after stopping
2:Valid during running, cleared after receiving the
stop command
LED thousands: ∧/∨ keys and digital
potentiometer integral function
0:The integral function is valid
1:The integral function is invalid
0.01~10.00s
0x00~0x221
LED ones: frequency control selection
0:UP/DOWN terminals setting valid
107
Function codes
Default
Modify
value
○
0x0000
○
0.10s
○
0x000
Need help?
Do you have a question about the GD200-037G/045P-4 and is the answer not in the manual?