Operating hours
An operating hours meter for the electronics is activated when the transmitter is first
started.
•
Open the View Menu Operating hours.
Switch Point adjustment
There are two switch points:
•
Switch point 1 (Off to On)
•
Switch point 2 (On to Off)
To adjust the switch behavior, set the percentage of the application range
the logic switch will change from OFF to ON, or from ON to OFF.
•
The application range must be defined first (see
setting
: and
setup procedure follows the guidelines for the application which most
resembles your operation).
•
Open the menu View–Display, and select the register Transducer Block:
Discrete Input, to view the actual Sensor Value, the Sensor Value Discrete, the
actual valid Switch Point and Hysteresis
•
Go to Input > Transducer Block: Discrete Input > Switch behavior.
•
Edit the value of Switch Point 1 in the "Switch Point" field.
•
Edit the value of Switch Point 2 to adjust the Hysteresis
•
Click on "Transmit" .
•
Track the effect of the adjustment by looking at the Sensor Value Discrete.
Resetting
To reset the device, open the Device Menu Master Reset. The three reset options are:
•
Factory reset (Restart/cold startup)
•
Warm start (new start-up)
•
Resetting the PROFIBUS address to 126
1.
The application range is defined by the 0% and 100% settings (see page 77).
Page IIC–84 Pointek CLS 200 (PROFIBUS PA) – INSTRUCTION MANUAL