Compact Operating Instructions
7ML5501 (Pointek CLS100, SS Process connection)
7ML5610 (Pointek CLS100, Plastic version)
05/2021
A5E32146158-AB
Introduction
Mounting
Connecting
Operation
Troubleshooting
Technical data
Dimensions
Notes for use in hazardous
locations
Product Documentation
and Technical Support
1
2
3
4
5
6
7
A
B

Advertisement

Table of Contents
loading

Summary of Contents for Siemens Pointek CLS100

  • Page 1 Mounting Pointek Connecting Operation Point level switches Pointek CLS100 Troubleshooting Technical data Compact Operating Instructions Dimensions Notes for use in hazardous locations Product Documentation and Technical Support 7ML5501 (Pointek CLS100, SS Process connection) 7ML5610 (Pointek CLS100, Plastic version) 05/2021 A5E32146158-AB...
  • Page 2 Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
  • Page 3: Table Of Contents

    Fully synthetic process connection (enclosure) ..............21 Maintenance ........................22 Technical data ............................23 Power ..........................23 Alarm output(s) ......................... 24 Environmental ........................25 Mechanical ........................26 Process conditions ......................26 Approvals .......................... 27 Dimensions ............................28 Dimensions........................28 Pointek CLS100 Compact Operating Instructions, 05/2021, A5E32146158-AB...
  • Page 4 Ambient and process temperature range, max. surface temperature and temperature class ..........................31 FM/CSA connection drawing ....................32 Product Documentation and Technical Support .................. 33 Product documentation ..................... 33 Technical support ......................34 Index ..............................35 Pointek CLS100 Compact Operating Instructions, 05/2021, A5E32146158-AB...
  • Page 5: Introduction

    Introduction Pointek CLS100 is a compact 2-wire capacitance switch for level detection in constricted spaces, interfaces, solids, liquids, slurries, and foam. The stainless steel process connection versions (7ML5501) have an effective process temperature range of -30 to +100 °C (-22 to +212 °F) and the synthetic process connection version (7ML5610) has an effective process...
  • Page 6: Mounting

    • When using multiple units, sensors must be 100 mm apart. Mount diagonally if vertical space is restricted. Pointek CLS100 is normally mounted into the vessel top (high detection alarm) or through the tank wall at the detection level (high or low detection alarm).
  • Page 7 Wall Restriction Process Cautions: • Keep out of path of falling material. • Consider material surface configuration when installing unit. • Protect probe from falling material. • Avoid areas where material buildup occurs. Pointek CLS100 Compact Operating Instructions, 05/2021, A5E32146158-AB...
  • Page 8: Connecting

    Aggressive substances, e.g. acidic liquids or gases that may attack metals, or solvents that may affect polymeric materials. Cable version ① Ground ② White ③ ④ Black Pointek CLS100 Compact Operating Instructions, 05/2021, A5E32146158-AB...
  • Page 9: Enclosure Version

    Cable shield ⑤ solid state switch/relay White wire relay available only on Pointek CLS100 fully synthetic enclosure version Note The mA current loop can be wired in either polarity to determine high or low level operation as shown in the examples beginning on Non-intrinsically-safe version (Page 11). The cable shield should be connected to terminal 3 on the terminal block along with the provided ground wire.
  • Page 10: Alarm Output Status

    High Alarm When material reaches a maximum process level, covering the probe. Low Alarm When material reaches a minimum process level, uncovering the probe. Pointek CLS100 Compact Operating Instructions, 05/2021, A5E32146158-AB...
  • Page 11: Power/Alarm Wiring

    Black ③ For more information, go to Enclosure version (Page 9). 5 and 4 are connected to Solid state switch output 2 and 1 are connected to 12-33 V DC (polarity determines operation) Pointek CLS100 Compact Operating Instructions, 05/2021, A5E32146158-AB...
  • Page 12 Stainless Steel Process Connection (Integral Cable or Enclosure Version) = (V - 12 V)/20 mA supply For example, 250 Ω gives 1 or 5 V DC switch voltage to PLC. Intrinsically Safe Version only Solid State Switch Application Pointek CLS100 Compact Operating Instructions, 05/2021, A5E32146158-AB...
  • Page 13: Intrinsically Safe Version Only

    Operation with 4/20 mA loop • For intrinsically safe operation, an intrinsic safety barrier is required. Ratings U of power supply • Rmax=(Vsupply - 12 V)/20 mA. Example: 24 V supply allows Rmax of 600 Ohms Pointek CLS100 Compact Operating Instructions, 05/2021, A5E32146158-AB...
  • Page 14: Enclosure Version And Fully Synthetic Process

    Operation with solid state switch/relay • Terminal 3 is internally connected to ground. It is recommended to use a shielded cable for stable measurement. • For intrinsically safe operation an intrinsically safe barrier is required. Ratings U Pointek CLS100 Compact Operating Instructions, 05/2021, A5E32146158-AB...
  • Page 15: Protection Diodes

    Always use a protection diode when driving an external relay with the solid state switch or relay contact. This prevents possible switch damage due to inductive spikes generated by the relay coil. Orient the diode based on the current flow. Pointek CLS100 Compact Operating Instructions, 05/2021, A5E32146158-AB...
  • Page 16 For integral cable equivalents, refer to Enclosure version (Page 9). CLS100 controlling the high side of the external relay (output acts like PNP transistor switch) CLS100 controlling the low side of the external relay (output acts like NPN transistor switch) Pointek CLS100 Compact Operating Instructions, 05/2021, A5E32146158-AB...
  • Page 17: Operation

    Follow the setup procedure associated with the case outline describing your application. Note that the sensitivity of the unit can be adjusted by the user as required. Case 1: General applications Characteristics • dry solids • low viscosity liquids Pointek CLS100 Compact Operating Instructions, 05/2021, A5E32146158-AB...
  • Page 18 Case 3: Interface detection Characteristics • liquid A / liquid B, foam / liquid Preparation • Ensure that the green LED is ON. • Turn the trimpot CCW (counter clockwise), until the yellow LED goes OFF. Pointek CLS100 Compact Operating Instructions, 05/2021, A5E32146158-AB...
  • Page 19 After completing the setup, replace the trimpot cap on the cable version, or the lid on the enclosure version. The unit is now in service, providing level detection of your process. Pointek CLS100 Compact Operating Instructions, 05/2021, A5E32146158-AB...
  • Page 20: Troubleshooting

    Red LED. Probable cause: wrong wiring in this circuit. Yellow LED is lit while probe is May indicate significant product Rotate sensitivity potentiometer not covered. buildup. further CCW (counter clockwise) Check sensor tip. Pointek CLS100 Compact Operating Instructions, 05/2021, A5E32146158-AB...
  • Page 21: Fully Synthetic Process Connection (Enclosure)

    DC for IS versions). versions). Defective component in device. Contact distributor. Yellow LED is lit while probe is May indicate significant product Rotate sensitivity potentiometer not covered. buildup. further CCW (counter clockwise) Check sensor tip. Pointek CLS100 Compact Operating Instructions, 05/2021, A5E32146158-AB...
  • Page 22: Maintenance

    Troubleshooting 5.3 Maintenance Maintenance The Pointek CLS100 requires no maintenance or cleaning. Pointek CLS100 Compact Operating Instructions, 05/2021, A5E32146158-AB...
  • Page 23: Technical Data

    = 2 nF* L = 1 mH *For an integral cable with a length of more than 1.5m a capacitance of 0.3 nF/ m shall be added For more information, see FM/CSA connection drawing (Page 32). Pointek CLS100 Compact Operating Instructions, 05/2021, A5E32146158-AB...
  • Page 24: Alarm Output(S)

    200 mA P = 1.5 W C = 2 nF* L = 1 mH *For an integral cable with a length of more than 1.5 m, a capacitance of 0.3 nF/m shall be added Pointek CLS100 Compact Operating Instructions, 05/2021, A5E32146158-AB...
  • Page 25: Environmental

    Depending on Surface Temperature and Tem- perature Class, details see Notes for use in hazardous locations (Page 30). ingress protec- Enclosure version Type 4 / IP68 tion Integral cable version Type 4 / IP65 installation category pollution degree Pointek CLS100 Compact Operating Instructions, 05/2021, A5E32146158-AB...
  • Page 26: Mechanical

    • With ATEX approval: – Depending on Surface Temperature and Temperature Class details, see Notes for use in hazardous locations (Page 30) • pressure (vessel): –1 to 10 bar (146 psi) gauge, nominal. Pointek CLS100 Compact Operating Instructions, 05/2021, A5E32146158-AB...
  • Page 27: Approvals

    EMC testing was conducted on the CLS100 metal version while mounted in a metallic vessel and wired using shielded cable. The sensitivity was set by turning sensitivity potentiometer 2 turns counter-clockwise from the set point. Pointek CLS100 Compact Operating Instructions, 05/2021, A5E32146158-AB...
  • Page 28: Dimensions

    ① Process connection ② Ground lug ③ Output status LED (Red) ④ Sensor status LED (Yellow) ⑤ Sensitivity trimpot ⑥ Power LED (Green) ⑦ Cable inlet 1/2" NPT (optional M20x1.5) ⑧ Terminal block Pointek CLS100 Compact Operating Instructions, 05/2021, A5E32146158-AB...
  • Page 29 Sensitivity trimpot ② Power LED (Green) ③ Ground post ④ Cable relief ⑤ Output status LED (Red) ⑥ Sensor status LED (Yellow) ⑦ Cable Ø 5 mm (0.2') ⑧ Trimpot cap ⑨ Process connection Pointek CLS100 Compact Operating Instructions, 05/2021, A5E32146158-AB...
  • Page 30: Notes For Use In Hazardous Locations

    Turn off power before servicing any device (the transmitter is in operation when the power supply is switched on). In case of removing the unit from vessel, take care of process pressure and material passing the opening. Pointek CLS100 Compact Operating Instructions, 05/2021, A5E32146158-AB...
  • Page 31: Specific Condition Of Use

    -30 to +45 °C (-22 to +113 -30 to +45 °C (-22 to +113 °F) 95 °C °F) -30 to +85 °C (-22 to +185 -30 to +85 °C (-22 to +185 °F) 135 °C °F) Pointek CLS100 Compact Operating Instructions, 05/2021, A5E32146158-AB...
  • Page 32: Fm/Csa Connection Drawing

    -30 to +100 °C (-22 to +212 °F) CSA: Ambient temperature range Process temperature range Temperature class -40 to +85 °C (-22 to +185 °F) -40 to +100 °C (-22 to +212 °F) FM/CSA connection drawing https://support.industry.siemens.com/cs/ww/en/view/109738929 Pointek CLS100 Compact Operating Instructions, 05/2021, A5E32146158-AB...
  • Page 33: Product Documentation And Technical Support

    Entering a serial number 1. Open the PIA Life Cycle Portal (https://www.pia-portal.automation.siemens.com). 2. Select the desired language. 3. Enter the serial number of your device. The product documentation relevant for your device is displayed and can be downloaded.
  • Page 34: Technical Support

    In addition to our technical support, Siemens offers comprehensive online services at Service & Support (http://www.siemens.com/automation/serviceandsupport). Contact If you have further questions about the device, contact your local Siemens representative at Personal Contact (http://www.automation.siemens.com/partner). To find the contact for your product, go to "all products and branches" and select "Products &...
  • Page 35: Index

    Customer Support, (Refer to Technical support) Downloads, 33 Hotline, (Refer to Support request) Manuals, 33 Service, 34 Service and support Internet, 34 Support, 34 Support request, 34 Technical support, 34 partner, 34 personal contact, 34 Pointek CLS100 Compact Operating Instructions, 05/2021, A5E32146158-AB...
  • Page 36 Index Pointek CLS100 Compact Operating Instructions, 05/2021, A5E32146158-AB...