Mode 14: Unit (default:
Note:
Mode 14 only becomes available after Electronics Temperature is selected in
Mode 13.
If Electronics Temperature is selected as the display source in Mode 13, you can change
the corresponding physical unit by selecting one of the following options:
Physical Unit
K
°C
°F
°R
To set the physical unit:
Select Mode 14: the primary reading field displays Unit, and the physical unit
appears in the auxiliary reading field.
Press ⇑ or ⇓ to select the desired physical unit.
Press M to exit.
Mode 15: Node address
Sets the node address of the device on PROFIBUS. The permitted range is from 0 to 126.
To set the PROFIBUS node address:
Select Mode 15. The current node address is shown in the primary reading field.
Press ⇑ or ⇓ to open Edit mode.
Enter the node address in the permitted range: press ⇑ to change the value of
each digit, and press ⇓ to move the cursor to the next digit.
Press ⇓ after editing the least significant digit, to terminate the procedure and to
save the value.
Press M to exit.
Note:
• While the device is in cyclic data exchange with a class 1 Master, it is not possible
to change the address. Abort the cyclic communication to change the address.
• Ensure that you set a unique node address to the device. Otherwise, the devices
with the same addresses will cause confusion on the bus.
1.
Not used for standalone device.
Page IIB–52 Pointek CLS 200 (standalone unit) – INSTRUCTION MANUAL
o
C)
Display
K
°C
°F
°R
1
(default: 3)
7ML19985AR02