Configuration
1.
Immerse the sensor in the material that has the lowest dielectric constant. L1 (yel-
low) should glow. If not, reset S5 to ON (high sensitivity).
2.
Adjust P2 counterclockwise until L1 stops glowing.
3.
Immerse the sensor in the material that has the highest dielectric constant. L1
should glow.
Delay alarm output
If you want to slow the Pointek CLS 200 response, to compensate for turbulence or false
readings, set a delay interval using potentiometer P1, and set S1 and/or S2 to OFF, to
enable the delay for either alarm activation, alarm de-activation, or both.
If an immediate alarm output is critical, set the appropriate switch to ON, to disable the
delay.
The functioning of S1 and S2 depends on the alarm setting:
High alarm/
overfill protection
Low alarm/
dry run protection
To test the delay function, follow the test procedure on page 18.
Operation
After completing the setup, replace the lid and secure the lid clip. Pointek CLS 200 (analog
model) is now ready to operate.
7ML19985AR02
Pointek CLS 200 (analog) – INSTRUCTION MANUAL
S1-ON disables delay of alarm de-activation (alarm OFF)
S2-ON disables delay of alarm activation (alarm ON)
S1-ON disables delay of alarm activation (alarm ON)
S2-ON disables delay of alarm de-activation (alarm OFF)
Page I – 25