Mode 16: PROFIBUS Ident Number
Determines which of two device operating modes to select. Pointek CLS 200 device
recognizes two operating modes in relation to the DP Master:
Mode
Description
0
Conforms to profile
version 3.0 Class B
device with no
extensions.
1
Conforms to profile
version 3.0 Class B
device with
extensions.
To set the device operating mode:
Select Mode 16. The current device operating Mode (0 or 1) appears in the
primary reading field.
Press ⇑ or ⇓ to select the desired operating mode.
Press M to exit.
Mode 19: 0% Application Range setting
This point corresponds to the left limit of the bar graph in the digital display.
For reliable and accurate detection of the process material, select the example in the
table below that most closely resembles your application, and adjust the setup conditions
accordingly.
.
Application
General
applications
Demanding
applications
Interface
detection
1.
Not used for standalone device.
7ML19985AR02
Pointek CLS 200 (standalone unit) – INSTRUCTION MANUAL Page IIB–53
Generic: can substitute transmitters conforming to
PROFIBUS PA profile 3.0, one Discrete Input
Function Block.
Device-Specific: full functional range of
Pointek CLS 200 with Discrete Input Function Block.
Material
dry solids
low viscosity liquids
hygroscopic / wet solids
high viscosity and high
conductivity liquids
liquid A / liquid B
foam / liquid
1
(default: 1)
Setup conditions
Sensor uncovered and a minimum of
100 mm (4") free space all around.
Sensor immersed and then uncovered,
but retaining as much buildup of
material as possible on the sensor.
Immerse the sensor in the material that
has the lowest dielectric constant.