Status
Status provides information on:
the usability of the measured value in the user programme
the device status (self-diagnosis/system diagnosis)
additional process information (process alarms)
The codes for the Status byte are listed in the following tables. Possible causes for an
error are given, along with measures to correct it
.
Digital
Hex
display
80
---
84
G_132
8D
G_141
8E
G_142
A4
G_164
a.
Set via PROFIBUS PA, in counts (see
Digital
Hex
display
00
---
0F
B_015
10
B_016
Page IIC–66
Pointek CLS 200 (PROFIBUS PA) – INSTRUCTION MANUAL
Status Codes for Good Quality
PDM display
Cause
Good
Normal operation
A parameter relevant for the
Good;
behavior of the device has
Active block alarm
been changed. The display is
extinguished after 10 seconds.
Good;
The Sensor Value exceeds the
Active critical alarm;
Lower Diagnostic Alarm Limit
Limit underflow
Good;
The Sensor Value exceeds the
Active critical alarm;
Upper Diagnostic Alarm Limit
Limit overflow
Good;
Maintenance interval has
Maintenance
expired
required
Status Codes for Bad Quality
PDM display
Cause
Is used if no other information is
Bad
available
Bad;
Device failure;
Device has an irreparable Error.
Value constant
Bad;
Sensor test failed
Sensor failure
Counts
an explanation of counts).
Corrective
Measure
---
Note to the control
system
Check installation and
a
sensor adjustment.
Check installation and
a
sensor adjustment.
Maintenance work,
electronics servicing,
or sensor servicing, is
required.
Corrective
Measure
Replace the
electronics.
Check sensor