.
Timer value
alarm
warning
warning occurred
warning acknowledged
alarm occurred
alarm acknowledged
OFF
reset
To edit the service intervals:
1.
Go to Diagnosis Settings
> Service interval for Electronics, or
> Service interval for Sensor
2.
Select a Warning/Alarm Activation setting.
3.
Set Single Values Input to Yes.
4.
Enter the time interval after which a warning should be issued.
5.
Enter the additional time interval after which an alarm should be issued, once a
warning has already occurred.
6.
Press Enter: the status field reads Changed.
Drag indicators
Two pairs of drag indicators allow you to monitor the negative and positive peak values
for the measured values Sensor Value and Electronics Temperature.
•
Open the View Menu Drag Indicators.
•
To reset the peaks to the actual measured value, click the appropriate Reset button.
•
Press Enter: the status field reads Changed
7ML19985AR02
Pointek CLS 200 (PROFIBUS PA) – INSTRUCTION MANUAL
Time
Page IIC–83