Remote Operation via PROFIBUS PA:
Pointek CLS 200
WARNING: It is essential to check settings during the process itself,
and confirm that they are correct, before regular operation commences.
The full range of Pointek CLS 200 functions is available only via remote operation using
PROFIBUS PA.
To use PROFIBUS PA, you will need a PC configuration tool: we recommend
SIMATIC PDM. Please consult the proprietary operating instructions or online help for
details on using SIMATIC PDM.
Measured Values
In measuring operations, measured values such as the logical level are provided via
PROFIBUS PA. PROFIBUS PA communication is indicated on the digital display by the
communication character o (see
Functions
The device menu gives you access to the following functions:
upload from/download to the device
set address
master reset
write locking
sensor test
simulation
Changing parameter settings
Note:
Initial setup can be carried out prior to mounting into the process, but it is
extremely important to calibrate the unit and adjust the sensitivity on the product itself.
First launch SIMATIC PDM, connect to Pointek CLS 200, and upload data from the
device (the status fields change to Loaded).
Adjust parameter values in the parameter view field (right side of screen).
After adjusting the value, press Enter (the status fields read Changed).
When you have completed the adjustments, open the Device menu, download data
to the device, and save parameter settings offline (the status fields go blank).