Mode 26: Switch Point 2/Falling Edge/ON to OFF
(default: 25%)
Note:
Initial setup can be carried out prior to mounting into the process, but it is
extremely important to calibrate the unit and adjust the sensitivity on the product itself.
Allows you to adjust the switch behavior by setting the percentage of the Application
Range (defined in Mode 19 and Mode 20) at which point the logical switch will change
from ON to OFF.
A downward step
indicator.
Switch Point 2 must have a value less than or equal to the value for Switch Point 1. If you
enter a higher value, Switch Point 1 will be adjusted to the same value.
If hysteresis
If hysteresis does not equal 0, you have two Switch Points in the Bar Graph: one for
Rising Edge (Switch Point 1), and one for Falling Edge (Switch Point 2).
To view the current setting for Switch Point 2:
Select Mode 26.
The current setting appears in the primary reading field.
Press M to exit, or:
To adjust the setting:
Press ⇑ or ⇓.
The display switches to the current measured Sensor Value in percent of the
Application Range (0 to 100%).
Press ⇑ or ⇓ to open Edit mode: the Sensor value is frozen.
Press ⇑ to edit the value of each digit, and press ⇓ to move the cursor to the
next digit.
After editing or leaving the least significant digit unchanged, press ⇓ to
terminate procedure and save the new value.
You see the new setting for Switch Point 2.
Repeat the process, or press M to exit.
1.
The difference in value between Switch Points 1 and 2.
Page IIB–58 Pointek CLS 200 (standalone unit) – INSTRUCTION MANUAL
appears to the left of the numerical value, as an additional
1
equals 0, you have one Switch Point in the Bar Graph
7ML19985AR02