Status Indicator Names - Omron 3G3AX-MX2-ECT User Manual

Mx2 series ethercat communication unit
Hide thumbs Also See for 3G3AX-MX2-ECT:
Table of Contents

Advertisement

2-1-2

Status Indicator Names

The following table shows the EtherCAT status indicators and their meanings.
Name
L/A IN
L/A OUT
RUN
ERR
Additional Information
The timing of each flashing state of indicator is as follows.
Flickering
Blinking
Single flash
Double flash
EtherCAT Communication Unit USER'S MANUAL (3G3AX-MX2-ECT)
Color
State
Green
OFF
ON
Flickering
Green
OFF
ON
Flickering
Green
OFF
Blinking
Single flash
ON
Red
OFF
Blinking
Single flash
Double flash
Flickering
ON
50
ms
on
off
on
200
200
ms
ms
off
on
200
ms
off
on
200
200
200
ms
ms
ms
off
2 Starting a Sample System
Meaning
Link not established in physical layer
Link established in physical layer
In operation after establishing link
Link not established in physical layer
Link established in physical layer
In operation after establishing link
Init state
Pre-operational state
Safe-operational state
Operational state
No error
Communications setting error
Synchronization error or communications data error
Application WDT timeout
Boot error
PDI WDT timeout
1000
200
ms
ms
1000
ms
2
2 - 3