Omron 3G3AX-MX2-ECT User Manual page 78

Mx2 series ethercat communication unit
Hide thumbs Also See for 3G3AX-MX2-ECT:
Table of Contents

Advertisement

Bit and data information
 Command
Bit
0
Forward/stop
1
Reverse/stop
7
Fault reset
-
Reserved
 Frequency reference
Name
Frequency reference
 Status
The 16-bit data is as shown below.
15
Bit
0
During forward operation
1
During reverse operation
3
Fault
7
Warning
9
Remote
12
Frequency matching
15
Connection error between the
Optional Unit and inverter
Reserved
 Output frequency monitor
Name
Output frequency monitor
EtherCAT Communication Unit USER'S MANUAL (3G3AX-MX2-ECT)
Name
0: Stop
1: Forward command
0: Stop
1: Reverse command
Set 0.
Specify the frequency reference in increments of 0.01 Hz. When a value is set that
exceeds the maximum frequency, operation is performed at the maximum frequency.
Setting range: 0 to maximum frequency
12
9
Name
0: Stopped/during reverse operation
1: During forward operation
0: Stopped/during forward operation
1: During reverse operation
0: No error or trip occurred for the unit or inverter
1: No error or trip occurred for the unit or inverter
0: No warning occurred for the unit or inverter
1: Warning occurred for the unit or inverter
0: Local (Operations from EtherCAT are disabled)
1: Remote (Operations from EtherCAT are enabled)
0: During acceleration/deceleration or stopped
1: Frequency matched
0: Normal
1: Error (Cannot update data for the inverter. To restore, turn the
Set 0.
Displays the output frequency in increments of 0.01 Hz.
7
Meaning
: Resets an error or trip for the unit or inverter.
Meaning
7
Meaning
power supply OFF and then ON again.)
Meaning
4 Inverter Control
1
3
1
4 - 11
0
4
0