Omron 3G3AX-MX2-ECT User Manual page 161

Mx2 series ethercat communication unit
Hide thumbs Also See for 3G3AX-MX2-ECT:
Table of Contents

Advertisement

Appendices
Event name
PDO Setting Error
Meaning
There is an illegal setting value in the PDO mapping.
Source
EtherCAT Master Function Module
Error attributes
Level
Effects
User program
Indicators
EtherCAT NET RUN
---
System-defined
Variable
variables
None
Cause and
Assumed cause
correction
The PDO mapping or SyncManager
settings are incorrect.
Attached
None
information
Precautions/
None
Remarks
A-40
Source details
Minor fault
Recovery
Continues.
Operation
EtherCAT NET ERR
---
Data type
---
Correction
Read and check the ALStatus code
and the value in 5200 hex. Correct the
settings.
EtherCAT Communication Unit USER'S MANUAL (3G3AX-MX2-ECT)
Event code
34F00000 hex
Slave
Detection
timing
Error reset (after
Log category
resetting slave
errors)
The slave can enter the Pre-operational state.
EtherCAT LINK/ACT
---
Name
---
Prevention
Check that there are no mistakes in
settings for the PDO mapping and
SyncManager.
At transfer of
EtherCAT Config-
uration Setup
System