Fault Reports - GE D30 Instruction Manual

Line distance protection system, ur series
Hide thumbs Also See for D30:
Table of Contents

Advertisement

6.4 RECORDS
6.4RECORDS
PATH: ACTUAL VALUES
NO FAULTS TO REPORT
or
 FAULT REPORT 1
The latest 15 fault reports can be stored. The most recent fault location calculation (when applicable) is displayed in this
menu, along with the date and time stamp of the event which triggered the calculation. See the

SETUP

FAULT REPORTS

menu for manual clearing of the fault reports and to the
CLEAR RECORDS
menu for automated clearing of the fault reports.
RECORDS
6
PATH: ACTUAL VALUES
 EVENT RECORDS
The event records menu shows the contextual data associated with up to the last 1024 events, listed in chronological order
from most recent to oldest. If all 1024 event records have been filled, the oldest record will be removed as a new record is
added. Each event record shows the event identifier/sequence number, cause, and date/time stamp associated with the
event trigger. See the
Only major output operands generate events, not every operand. Elements that assert output per phase, for example, log
operating phase output only without asserting the common three-phase operand event.
6-24

RECORDS
FAULT REPORTS
FAULT 1
LINE ID: SRC 1
FAULT 1
MESSAGE
2000/08/11
FAULT 1
MESSAGE
00:00:00.000000
FAULT 1
MESSAGE
ABG
FAULT 1
MESSAGE
00.0 km
FAULT 1
MESSAGE
SHOT: 0
menu for assigning the source and trigger for fault calculations. Refer to the

RECORDS
EVENT RECORDS
EVENT: XXXX
RESET OP(PUSHBUTTON)
EVENT: 3
MESSAGE
POWER ON
EVENT: 2
MESSAGE
POWER OFF
EVENT: 1
MESSAGE
EVENTS CLEARED
COMMANDS
CLEAR RECORDS
D30 Line Distance Protection System
FAULT REPORT 1(15)
Range: SRC 1, SRC 2
Range: YYYY/MM/DD
DATE:
Range: HH:MM:SS.ssssss
TIME:
Range: not available if the source VTs are in the "Delta"
TYPE:
configuration
Range: not available if the source VTs are in the "Delta"
LOCATION
configuration
Range: where applicable
RECLOSE
SETTINGS
menu for clearing event records.
6 ACTUAL VALUES
6.4.1 FAULT REPORTS
SETTINGS
PRODUCT
COMMANDS

PRODUCT SETUP
CLEAR RELAY
6.4.2 EVENT RECORDS
EVENT 3
DATE: 2000/07/14
EVENT 3
TIME: 14:53:00.03405
Date and Time Stamps