5.6 GROUPED ELEMENTS
5
c) GROUND DISTANCE (ANSI 21G)

PATH: SETTINGS
GROUPED ELEMENTS
 GROUND DISTANCE Z1
5-152
Figure 5–64: PHASE DISTANCE SCHEME LOGIC
SETTING GROUP 1(6)
GND DIST Z1
FUNCTION: Disabled
GND DIST Z1 DIR:
MESSAGE
Forward
GND DIST Z1
MESSAGE
SHAPE: Mho
GND DIST Z1
MESSAGE
Z0/Z1 MAG: 2.70
GND DIST Z1
MESSAGE
Z0/Z1 ANG: 0°
GND DIST Z1
MESSAGE
ZOM/Z1 MAG: 0.00
GND DIST Z1
MESSAGE
ZOM/Z1 ANG: 0°
D30 Line Distance Protection System


DISTANCE
GROUND DISTANCE Z1(Z5)
Range: Disabled, Enabled
Range: Forward, Reverse, Non-directional
Range: Mho, Quad
Range: 0.00 to 10.00 in steps of 0.01
Range: –90 to 90° in steps of 1
Range: 0.00 to 7.00 in steps of 0.01
Range: –90 to 90° in steps of 1