5.9 TRANSDUCER INPUTS AND OUTPUTS
Table 5–34: RTD TEMPERATURE VS. RESISTANCE
TEMPERATURE
°C
°F
–50
–58
–40
–40
–30
–22
–20
–4
–10
14
0
32
10
50
20
68
30
86
40
104
50
122
60
140
70
158
80
176
90
194
100
212
110
230
5
120
248
130
266
140
284
150
302
160
320
170
338
180
356
190
374
200
392
210
410
220
428
230
446
240
464
250
482
5-262
RESISTANCE (IN OHMS)
100 Ω PT
120 Ω NI
100 Ω NI
(DIN 43760)
80.31
86.17
71.81
84.27
92.76
77.30
88.22
99.41
82.84
92.16
106.15
88.45
96.09
113.00
94.17
100.00
120.00
100.00
103.90
127.17
105.97
107.79
134.52
112.10
111.67
142.06
118.38
115.54
149.79
124.82
119.39
157.74
131.45
123.24
165.90
138.25
127.07
174.25
145.20
130.89
182.84
152.37
134.70
191.64
159.70
138.50
200.64
167.20
142.29
209.85
174.87
146.06
219.29
182.75
149.82
228.96
190.80
153.58
238.85
199.04
157.32
248.95
207.45
161.04
259.30
216.08
164.76
269.91
224.92
168.47
280.77
233.97
172.46
291.96
243.30
175.84
303.46
252.88
179.51
315.31
262.76
183.17
327.54
272.94
186.82
340.14
283.45
190.45
353.14
294.28
194.08
366.53
305.44
D30 Line Distance Protection System
10 Ω CU
7.10
7.49
7.88
8.26
8.65
9.04
9.42
9.81
10.19
10.58
10.97
11.35
11.74
12.12
12.51
12.90
13.28
13.67
14.06
14.44
14.83
15.22
15.61
16.00
16.39
16.78
17.17
17.56
17.95
18.34
18.73