5.2 PRODUCT SETUP
k) DNP / IEC 60870-5-104 POINT LISTS
PATH: SETTINGS
PRODUCT SETUP
DNP / IEC104
POINT LISTS
Up to 256 binary and up to 256 analog input points for the DNP protocol, or the MSP and MME points for IEC 60870-5-104
protocol, can be configured. The value for each point is user-programmable and can be configured by assigning FlexLogic
operands for binary inputs / MSP points or FlexAnalog parameters for analog inputs / MME points.
The menu for the binary input points (DNP) or MSP points (IEC 60870-5-104) is shown below.
PATH: SETTINGS
PRODUCT SETUP
BINARY INPUT / MSP
POINTS
Up to 256 binary input points can be configured for the DNP or IEC 60870-5-104 protocols. The points are configured by
5
assigning an appropriate FlexLogic operand. See the Introduction to FlexLogic section in this chapter for the full range of
assignable operands.
The menu for the analog input points (DNP) or MME points (IEC 60870-5-104) is shown below.
PATH: SETTINGS
PRODUCT SETUP
ANALOG INPUT / MME
POINTS
Up to 256 analog input points can be configured for the DNP or IEC 60870-5-104 protocols. The analog point list is config-
ured by assigning an appropriate FlexAnalog parameter to each point. Refer to Appendix A: FlexAnalog Parameters for the
full range of assignable parameters.
The DNP / IEC 60870-5-104 point lists always begin with point 0 and end at the first "Off" value. Since DNP / IEC
60870-5-104 point lists must be in one continuous block, any points assigned after the first "Off" point are ignored.
NOTE
Changes to the DNP / IEC 60870-5-104 point lists will not take effect until the D30 is restarted.
NOTE
5-40
COMMUNICATIONS
BINARY INPUT / MSP
POINTS
ANALOG INPUT / MME
MESSAGE
POINTS
COMMUNICATIONS
Point:
Off
Point:
MESSAGE
Off
Point:
MESSAGE
Off
COMMUNICATIONS
Point:
Off
Point:
MESSAGE
Off
Point:
MESSAGE
Off
D30 Line Distance Protection System
DNP / IEC104 POINT LISTS
Range: see sub-menu below
Range: see sub-menu below
DNP / IEC104 POINT LISTS
Range: FlexLogic operand
0
Range: FlexLogic operand
1
↓
Range: FlexLogic operand
255
DNP / IEC104 POINT LISTS
Range: any FlexAnalog parameter
0
Range: any FlexAnalog parameter
1
↓
Range: any FlexAnalog parameter
255
5 SETTINGS
BINARY INPUT / MSP POINTS
ANALOG INPUT / MME POINTS
GE Multilin