Pre-Fault Setup - GE 489 Instruction Manual

Generator management relay
Hide thumbs Also See for 489:
Table of Contents

Advertisement

4 SETPOINTS
PATH: SETPOINTS
S12 TESTING

PRE-FAULT SETUP

[ENTER] for more
The values entered under Pre-Fault Values will be substituted for the measured values in the 489 when the
is "Simulate Pre-Fault".
MODE
GE Multilin
PRE-FAULT SETUP
ð
PRE-FAULT Iphase
ENTER
ð
ESCAPE
OUTPUT: 0.00 x CT
PRE-FAULT VOLTAGES
ESCAPE
PHASE-N: 1.00 x Rated
MESSAGE
PRE-FAULT CURRENT
ESCAPE
LAGS VOLTAGE: 0°
MESSAGE
PRE-FAULT Iphase
ESCAPE
NEUTRAL: 0.00 x CT
MESSAGE
PRE-FAULT CURRENT
ESCAPE
GROUND: 0.00 x CT
MESSAGE
PRE-FAULT VOLTAGE
ESCAPE
NEUTRAL: 0 Vsec
MESSAGE
PRE-FAULT STATOR
ESCAPE
RTD TEMP: 40°C
MESSAGE
PRE-FAULT BEARING
ESCAPE
RTD TEMP: 40°C
MESSAGE
PRE-FAULT OTHER
ESCAPE
RTD TEMP: 40°C
MESSAGE
PRE-FAULT AMBIENT
ESCAPE
RTD TEMP: 40°C
MESSAGE
PRE-FAULT SYSTEM
ESCAPE
FREQUENCY: 60.0 Hz
MESSAGE
PRE-FAULT ANALOG
ESCAPE
INPUT 1: 0%
MESSAGE
PRE-FAULT ANALOG
ESCAPE
INPUT 2: 0%
MESSAGE
PRE-FAULT ANALOG
ESCAPE
INPUT 3: 0%
MESSAGE
PRE-FAULT ANALOG
ESCAPE
INPUT 4: 0%
MESSAGE
489 Generator Management Relay
4.13 S12 TESTING
4.13.2 PRE-FAULT SETUP
Range: 0.00 to 20.00 × CT in steps of 0.01
Range: 0.00 to 1.50 × Rated in steps of 0.01
Entered as a phase-to-neutral quantity.
Range: 0 to 359° in steps of 1
Range: 0.00 to 20.00 × CT in steps of 0.01
180° phase shift with respect to Iphase OUTPUT
Range: 0.00 to 20.00 × CT in steps of 0.01
CT is either XXX:1 or 50:0.025
Range
0.0 to 100.0 Vsec in steps of 0.1
Fundamental value only in secondary units
Range: –50 to 250°C in steps of 1
Range: –50 to 250°C in steps of 1
Range: –50 to 250°C in steps of 1
Range: –50 to 250°C in steps of 1
Range: 5.0 to 90.0 Hz in steps of 0.1
Range: 0 to 100% in steps of 1
Range: 0 to 100% in steps of 1
Range: 0 to 100% in steps of 1
Range: 0 to 100% in steps of 1
4
SIMULATION
4-79

Advertisement

Table of Contents
loading

Table of Contents