GE D30 Instruction Manual page 330

Line distance protection system, ur series
Hide thumbs Also See for D30:
Table of Contents

Advertisement

5.6 GROUPED ELEMENTS
c) NEGATIVE SEQUENCE INSTANTANEOUS OVERCURRENT (ANSI 50Q, IEC PIOC)

PATH: SETTINGS
GROUPED ELEMENTS
 NEG SEQ IOC1
The negative-sequence instantaneous overcurrent element may be used as an instantaneous function with no intentional
5
delay or as a definite time function. The element responds to the negative-sequence current fundamental frequency phasor
magnitude (calculated from the phase currents) and applies a positive-sequence restraint for better performance: a small
portion (12.5%) of the positive-sequence current magnitude is subtracted from the negative-sequence current magnitude
when forming the operating quantity:
The positive-sequence restraint allows for more sensitive settings by counterbalancing spurious negative-sequence cur-
rents resulting from:
system unbalances under heavy load conditions
transformation errors of current transformers (CTs) during three-phase faults
fault inception and switch-off transients during three-phase faults
The positive-sequence restraint must be considered when testing for pickup accuracy and response time (multiple of
pickup). The operating quantity depends on the way the test currents are injected into the relay (single-phase injection:
I
0.2917 I
=
op
injected
5-194
SETTING GROUP 1(6)
NEG SEQ IOC1
FUNCTION: Disabled
NEG SEQ IOC1 SIGNAL
MESSAGE
SOURCE: SRC 1
NEG SEQ IOC1
MESSAGE
PICKUP: 1.000 pu
NEG SEQ IOC1 PICKUP
MESSAGE
DELAY:
NEG SEQ IOC1 RESET
MESSAGE
DELAY:
NEG SEQ IOC1 BLOCK:
MESSAGE
Off
NEG SEQ IOC1
MESSAGE
TARGET: Self-reset
NEG SEQ IOC1
MESSAGE
EVENTS: Disabled
I
I_2
K I_1
=
op
; three-phase injection, opposite rotation:
Figure 5–91: NEGATIVE SEQUENCE IOC1 SCHEME LOGIC
D30 Line Distance Protection System

NEGATIVE SEQUENCE CURRENT
Range: Disabled, Enabled
Range: SRC 1, SRC 2
Range: 0.000 to 30.000 pu in steps of 0.001
Range: 0.00 to 600.00 s in steps of 0.01
0.00 s
Range: 0.00 to 600.00 s in steps of 0.01
0.00 s
Range: FlexLogic operand
Range: Self-reset, Latched, Disabled
Range: Disabled, Enabled
1 8 ⁄
where K
=
I
I
).
=
op
injected
5 SETTINGS

NEG SEQ OC1(2)
(EQ 5.18)
GE Multilin