GE D30 Instruction Manual page 568

Line distance protection system, ur series
Hide thumbs Also See for D30:
Table of Contents

Advertisement

B.4 MEMORY MAPPING
Table B–10: MODBUS MEMORY MAP (Sheet 62 of 62)
ADDR
REGISTER NAME
D8AA
...Repeated for DCmA Inputs 15
D8BD
...Repeated for DCmA Inputs 16
D8D0
...Repeated for DCmA Inputs 17
D8E3
...Repeated for DCmA Inputs 18
D8F6
...Repeated for DCmA Inputs 19
B
D909
...Repeated for DCmA Inputs 20
D91C
...Repeated for DCmA Inputs 21
D92F
...Repeated for DCmA Inputs 22
D942
...Repeated for DCmA Inputs 23
D955
...Repeated for DCmA Inputs 24
DNP/IEC Points (Read/Write Setting)
D968
DNP/IEC 60870-5-104 Binary Input Points (256 items)
DB68
DNP/IEC 60870-5-104 Analog Input Points (256 items)
Synchrocheck (Read/Write Setting) (4 modules)
DC70
Synchrocheck 1 Function
DC71
Synchrocheck 1 V1 Source
DC72
Synchrocheck 1 V2 Source
DC73
Synchrocheck 1 Maximum Voltage Difference
DC75
Synchrocheck 1 Maximum Angle Difference
DC76
Synchrocheck 1 Maximum Frequency Difference
DC77
Synchrocheck 1 Dead Source Select
DC78
Synchrocheck 1 Dead V1 Maximum Voltage
DC79
Synchrocheck 1 Dead V2 Maximum Voltage
DC7A
Synchrocheck 1 Live V1 Minimum Voltage
DC7B
Synchrocheck 1 Live V2 Minimum Voltage
DC7C
Synchrocheck 1 Target
DC7D
Synchrocheck 1 Events
DC7E
Synchrocheck 1 Block
DC80
Synchrocheck 1 Frequency Hysteresis
DC81
...Repeated for Synchrocheck 2
DC92
...Repeated for Synchrocheck 3
DCA3
...Repeated for Synchrocheck 4
Settings File Template (Read/Write Setting)
ED00
FlexLogic Displays Active
ED01
Template Access
Setting File Template (Read Only Non-Volatile)
ED07
Last Settings Change Date
Settings File Template (Read/Write Setting)
ED09
Template Bitmask (750 items)
B-70
RANGE
0 to 4294967295
0 to 65535
0 to 1
0 to 5
0 to 5
0 to 400000
0 to 100
0 to 2
0 to 5
0 to 1.25
0 to 1.25
0 to 1.25
0 to 1.25
0 to 2
0 to 1
0 to 4294967295
0 to 0.1
0 to 1
---
0 to 4294967295
0 to 65535
D30 Line Distance Protection System
APPENDIX B
UNITS
STEP
FORMAT
---
1
F300
---
1
F600
---
1
F102
---
1
F167
---
1
F167
V
1
F060
degrees
1
F001
Hz
0.01
F001
---
1
F176
1 (LV1 and DV2)
pu
0.01
F001
pu
0.01
F001
pu
0.01
F001
pu
0.01
F001
---
1
F109
---
1
F102
---
1
F300
Hz
0.01
F001
---
1
F102
---
---
F205
---
1
F050
---
1
F001
DEFAULT
0
0
0 (Disabled)
0 (SRC 1)
1 (SRC 2)
10000
30
100
30
30
70
70
0 (Self-reset)
0 (Disabled)
0
6
1 (Enabled)
(none)
0
0
GE Multilin

Advertisement

Table of Contents
loading

Table of Contents