GE D30 Instruction Manual page 527

Line distance protection system, ur series
Hide thumbs Also See for D30:
Table of Contents

Advertisement

APPENDIX B
Table B–10: MODBUS MEMORY MAP (Sheet 21 of 62)
ADDR
REGISTER NAME
40EE
IEC 60870-5-104 Other Default Threshold
40F0
IEC 60870-5-104 Client Address (5 items)
4104
IEC 60870-5-104 Redundancy Port Enabled/Disabled
4105
Port 2 IP Address
4107
Port 2 IP Subnet Mask
4109
Port 2 Gateway IP Address
410B
PRT2 Ethernet Operation Mode
410C
PRT2 Redundancy Enabled
410D
Port 3 IP Address
410F
Port 3 IP Subnet Mask
4111
Port 3 Gateway IP Address
4113
Port 3 Ethernet Operation Mode
4114
PRT1 GOOSE Enabled
4115
PRT2 GOOSE Enabled
4116
PRT3 GOOSE Enabled
4117
Default IPv4 Route
4119
PRT2 PRP Mcst Addr
411C
IEC Communications Reserved (33 items)
413E
High Enet Traffic Function
413F
High Enet Traffic Events
4140
DNP Object 1 Default Variation
4141
DNP Object 2 Default Variation
4142
DNP Object 20 Default Variation
4143
DNP Object 21 Default Variation
4144
DNP Object 22 Default Variation
4145
DNP Object 23 Default Variation
4146
DNP Object 30 Default Variation
4147
DNP Object 32 Default Variation
4148
SCADA Protocol
Communications Actual Values (Read Only)
4160
Modbus Available TCP/IP Connections
4161
DNP Available TCP/IP Connections
4162
IEC Available TCP/IP Connections
4163
MMS Available TCP/IP Connections
4164
PMU Available TCP/IP Connections
Simple Network Time Protocol (Read/Write Setting)
4168
Simple Network Time Protocol (SNTP) Function
4169
Simple Network Time Protocol (SNTP) Server IP Address
416B
Simple Network Time Protocol (SNTP) UDP Port Number
Clock (Read/Write Setting)
419F
Synchronizing Source
Clock (Read/Write Command)
41A0
Real Time Clock Set Time
Clock (Read/Write Setting)
41A2
SR Date Format
41A4
SR Time Format
41A6
IRIG-B Signal Type
41A7
Clock Events Enable / Disable
41A8
Time Zone Offset from UTC
41A9
Daylight Savings Time (DST) Function
41AA
Daylight Savings Time (DST) Start Month
41AB
Daylight Savings Time (DST) Start Day
41AC
Daylight Savings Time (DST) Start Day Instance
41AD
Daylight Savings Time (DST) Start Hour
GE Multilin
RANGE
0 to 100000000
0 to 4294967295
0 to 1
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 1
0 to 2
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 1
0 to 1
0 to 1
0 to 1
0 to 4294967295
---
0 to 1
0 to 1
0 to 1
1 to 2
1 to 3
0 to 3
0 to 3
0 to 3
0 to 3
1 to 5
0 to 5
0 to 2
0 to 4
0 to 2
0 to 2
0 to 5
0 to 4
0 to 1
0 to 4294967295
1 to 65535
0 to 3
0 to 235959
0 to 4294967295
0 to 4294967295
0 to 2
0 to 1
–24 to 24
0 to 1
0 to 11
0 to 6
0 to 4
0 to 23
D30 Line Distance Protection System
B.4 MEMORY MAPPING
UNITS
STEP
FORMAT
---
1
F003
---
1
F003
---
1
F126
---
1
F003
---
1
F003
---
1
F003
---
1
F192
1 (Full-Duplex)
---
1
F627
---
1
F003
---
1
F003
---
1
F003
---
1
F192
1 (Full-Duplex)
---
1
F102
---
1
F102
---
1
F102
---
1
F003
---
---
F072
---
1
F001
---
1
F102
---
1
F102
---
1
F001
---
1
F001
---
1
F523
---
1
F524
---
1
F523
---
1
F523
---
1
F001
---
1
F525
---
1
F629
---
1
F001
---
1
F001
---
1
F001
---
1
F001
---
1
F001
---
1
F102
---
1
F003
---
1
F001
---
1
F623
---
1
F050
---
1
F051
---
1
F052
---
1
F114
---
1
F102
hours
0.5
F002
---
1
F102
---
1
F237
---
1
F238
---
1
F239
---
1
F001
DEFAULT
30000
0
0 (No)
2130706433
4278190080
B
56554497
0 (None)
2130706433
4278190080
56554497
1 (Enabled)
1 (Enabled)
1 (Enabled)
2130706433
0
0
0 (Disabled)
0 (Disabled)
2
2
0 (1)
0 (1)
0 (1)
0 (1)
1
0 (1)
0 (DNP 3.0)
4
2
2
5
4
0 (Disabled)
0
123
0 (None)
0
0
0
0 (None)
0 (Disabled)
0
0 (Disabled)
0 (January)
0 (Sunday)
0 (First)
2
B-29

Advertisement

Table of Contents
loading

Table of Contents