6.3 METERING
The metered values for real, reactive, and apparent power, as well as power factor, are displayed in this menu. The "SRC
1" text is replaced by whatever name was programmed by the user for the associated source (see

SETUP
SIGNAL SOURCES
When VTs are configured in wye, the D30 calculates power in each phase and three-phase power is measured as
When VTs are configured in delta, the D30 does not calculate power in each phase and three-phase power is measured as
where
S is the apparent power
V
, V
, V
, I
, I
, I
are phase voltage and phase current phasors
A
B
C
A
B
C
V
and V
are phase-to-phase voltage phasors
AB
CB
Î is the conjugate of I
g) FREQUENCY METERING
PATH: ACTUAL VALUES
 FREQUENCY
 SRC 1
6
The metered frequency values are displayed in this menu. The "SRC 1" text will be replaced by whatever name was pro-
grammed by the user for the associated source (see
is measured via software-implemented zero-crossing detection of an AC signal. The signal is either a
SOURCE FREQUENCY
Clarke transformation of three-phase voltages or currents, auxiliary voltage, or ground current as per source configuration
(see the
SYSTEM SETUP
final frequency measurement is passed through a validation filter that eliminates false readings due to signal distortions and
transients.
PATH: ACTUAL VALUES
 SYNCHROCHECK 1
If a synchrocheck function setting is "Disabled", the corresponding actual values menu item is not displayed.
6-18
SRC 1
POWER FACTOR
MESSAGE
φa:
SRC 1
POWER FACTOR
MESSAGE
φb:
SRC 1
POWER FACTOR
MESSAGE
φc:
).
S = V
x Î
A
S = V

METERING
SOURCE SRC 1
SRC 1
FREQUENCY:
0.00 Hz

settings). The signal used for frequency estimation is low-pass filtered. The
POWER SYSTEM


METERING

SYNCHROCHECK

SYNCHROCHECK 1 DELTA
VOLT:
0.000 V
SYNCHROCHECK 1 DELTA
MESSAGE
PHASE:
SYNCHROCHECK 1 DELTA
MESSAGE
FREQ:
D30 Line Distance Protection System
1.000
1.000
1.000
+ V
x Î
+ V
x Î
A
B
B
C
C
x Î
+ V
x Î
AB
A
CB
C

FREQUENCY

SETTINGS
SYSTEM SETUP
SYNCHROCHECK 1(4)
0.0°
0.00 Hz
6 ACTUAL VALUES

SETTINGS

).
SIGNAL SOURCES
6.3.3 SYNCHROCHECK
SYSTEM
(EQ 6.1)
(EQ 6.2)
GE Multilin