6.3 METERING
PATH: ACTUAL VALUES
 FLEXELEMENT 1
The operating signals for the FlexElements are displayed in pu values using the following definitions of the base units.
Table 6–2: FLEXELEMENT BASE UNITS
BREAKER ACC ARCING AMPS
(Brk X Acc Arc Amp A, B, and C)
BREAKER ARCING AMPS
(Brk X Arc Amp A, B, and C)
DCmA
FAULT LOCATION
FREQUENCY
PHASE ANGLE
POWER FACTOR
RTDs
SOURCE CURRENT
SOURCE POWER
SOURCE VOLTAGE
SYNCHROCHECK
(Max Delta Volts)
Z
BASE
6
PATH: ACTUAL VALUES
 IEC 61850
 GOOSE ANALOGS
The D30 Line Distance Protection System is provided with optional IEC 61850 communications capability.
This feature is specified as a software option at the time of ordering. See the Order Codes section of chap-
ter 2 for details.
6-20


METERING

FLEXELEMENTS

FLEXELEMENT 1
OpSig: 0.000 pu
2
BASE = 2000 kA
2
BASE = 1 kA
× cycle
BASE = maximum value of the
under the +IN and –IN inputs.
BASE = Line Length as specified in Fault Report
f
= 1 Hz
BASE
ϕ
= 360 degrees (see the UR angle referencing convention)
BASE
PF
= 1.00
BASE
BASE = 100°C
I
= maximum nominal primary RMS value of the +IN and –IN inputs
BASE
P
= maximum value of V
BASE
V
= maximum nominal primary RMS value of the +IN and –IN inputs
BASE
V
= maximum primary RMS value of all the sources related to the +IN and –IN inputs
BASE
Z
= PhaseVTSecondary / PhaseCTSecondary, where PhaseVTSecondary and
BASE
PhaseCTSecondary are the secondary nominal voltage and the secondary nominal current of the
distance source. In case multiple CT inputs are summed as one source current and mapped as
the distance source, use the PhaseCTSecondary value from the CT with the highest primary
nominal current.
Distance source is specified in setting under
GROUP 1(6) > DISTANCE
PhaseVTSecondary and PhaseCTSecondary are specified in setting under
SETUP > AC INPUTS


METERING
IEC 61850 GOOSE ANALOGS
ANALOG INPUT
0.000
ANALOG INPUT
MESSAGE
0.000
ANALOG INPUT
MESSAGE
0.000
ANALOG INPUT 32
MESSAGE
0.000
D30 Line Distance Protection System
FLEXELEMENT 1(8)
× cycle
DCMA INPUT MAX
setting for the two transducers configured
× I
for the +IN and –IN inputs
BASE
BASE
SETTINGS > GROUPED ELEMENTS > SETTING
.
.
6.3.6 IEC 61580 GOOSE ANALOG VALUES
1
2
3
6 ACTUAL VALUES
6.3.5 FLEXELEMENTS
SETTINGS > SYSTEM