GE D30 Instruction Manual page 261

Line distance protection system, ur series
Hide thumbs Also See for D30:
Table of Contents

Advertisement

5 SETTINGS
Table 5–14: D30 FLEXLOGIC OPERANDS (Sheet 7 of 8)
OPERAND TYPE
OPERAND SYNTAX
INPUTS/OUTPUTS:
Virt Ip 1
Virtual inputs
Virt Ip 2
Virt Ip 3
Virt Ip 64
INPUTS/OUTPUTS:
Virt Op 1
Virtual outputs
Virt Op 2
Virt Op 3
Virt Op 96
LED INDICATORS:
LED IN SERVICE
Fixed front panel
LED TROUBLE
LEDs
LED TEST MODE
LED TRIP
LED ALARM
LED PICKUP
LED VOLTAGE
LED CURRENT
LED FREQUENCY
LED OTHER
LED PHASE A
LED PHASE B
LED PHASE C
LED NEUTRAL/GROUND
LED INDICATORS:
LED TEST IN PROGRESS
LED test
LED INDICATORS:
LED USER 1
User-programmable
LED USER 2 to 48
LEDs
PASSWORD
ACCESS LOC SETG OFF
SECURITY
ACCESS LOC SETG ON
ACCESS LOC CMND OFF
ACCESS LOC CMND ON
ACCESS REM SETG OFF
ACCESS REM SETG ON
ACCESS REM CMND OFF
ACCESS REM CMND ON
UNAUTHORIZED ACCESS
REMOTE DEVICES
REMOTE DEVICE 1 On
REMOTE DEVICE 2 On
REMOTE DEVICE 3 On
REMOTE DEVICE 16 On
REMOTE DEVICE 1 Off
REMOTE DEVICE 2 Off
REMOTE DEVICE 3 Off
REMOTE DEVICE 16 Off
RESETTING
RESET OP
RESET OP (COMMS)
RESET OP (OPERAND)
RESET OP (PUSHBUTTON)
GE Multilin
OPERAND DESCRIPTION
On
Flag is set, logic=1
On
Flag is set, logic=1
On
Flag is set, logic=1
On
Flag is set, logic=1
On
Flag is set, logic=1
On
Flag is set, logic=1
On
Flag is set, logic=1
On
Flag is set, logic=1
Asserted when the front panel IN SERVICE LED is on
Asserted when the front panel TROUBLE LED is on
Asserted when the front panel TEST MODE LED is on
Asserted when the front panel TRIP LED is on
Asserted when the front panel ALARM LED is on
Asserted when the front panel PICKUP LED is on
Asserted when the front panel VOLTAGE LED is on
Asserted when the front panel CURRENT LED is on
Asserted when the front panel FREQUENCY LED is on
Asserted when the front panel OTHER LED is on
Asserted when the front panel PHASE A LED is on
Asserted when the front panel PHASE B LED is on
Asserted when the front panel PHASE C LED is on
Asserted when the front panel NEUTRAL/GROUND LED is on
An LED test has been initiated and has not finished
Asserted when user-programmable LED 1 is on
The operand above is available for user-programmable LEDs 2 through 48
Asserted when local setting access is disabled
Asserted when local setting access is enabled
Asserted when local command access is disabled
Asserted when local command access is enabled
Asserted when remote setting access is disabled
Asserted when remote setting access is enabled
Asserted when remote command access is disabled
Asserted when remote command access is enabled
Asserted when a password entry fails while accessing a password protected
level of the D30
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
Reset command is operated (set by all three operands below)
Communications source of the reset command
Operand (assigned in the
of the reset command
Reset key (pushbutton) source of the reset command
D30 Line Distance Protection System
5.5 FLEXLOGIC
INPUTS/OUTPUTS

RESETTING
5
menu) source
5-125

Advertisement

Table of Contents
loading

Table of Contents