5.6 GROUPED ELEMENTS
g) AUXILIARY OVERVOLTAGE (ANSI 59X, IEC PTOV)

PATH: SETTINGS
GROUPED ELEMENTS
 AUXILIARY OV1
The D30 contains one auxiliary overvoltage element for each VT bank. This element is intended for monitoring overvoltage
5
conditions of the auxiliary voltage. The nominal secondary voltage of the auxiliary voltage channel entered under

SETUP
AC INPUTS
pickup level.
A typical application for this element is monitoring the zero-sequence voltage (3V_0) supplied from an open-corner-delta
VT connection.
5-206
SETTING GROUP 1(6)
AUX OV1
FUNCTION: Disabled
AUX OV1 SIGNAL
MESSAGE
SOURCE: SRC 1
AUX OV1 PICKUP:
MESSAGE
0.300 pu
AUX OV1 PICKUP
MESSAGE
DELAY: 1.00 s
AUX OV1 RESET
MESSAGE
DELAY: 1.00 s
AUX OV1 BLOCK:
MESSAGE
Off
AUX OV1 TARGET:
MESSAGE
Self-reset
AUX OV1 EVENTS:
MESSAGE
Disabled

VOLTAGE BANK X5
AUXILIARY VT X5 SECONDARY
Figure 5–100: AUXILIARY OVERVOLTAGE SCHEME LOGIC
D30 Line Distance Protection System


VOLTAGE ELEMENTS
AUXILIARY OV1
Range: Disabled, Enabled
Range: SRC 1, SRC 2
Range: 0.000 to 3.000 pu in steps of 0.001
Range: 0.00 to 600.00 s in steps of 0.01
Range: 0.00 to 600.00 s in steps of 0.01
Range: FlexLogic operand
Range: Self-reset, Latched, Disabled
Range: Disabled, Enabled
is the per-unit (pu) base used when setting the