GE D30 Instruction Manual page 334

Line distance protection system, ur series
Hide thumbs Also See for D30:
Table of Contents

Advertisement

5.6 GROUPED ELEMENTS
NEG SEQ DIR OC1 FWD PICKUP: This setting defines the pickup level for the overcurrent unit in the forward direc-
tion. Upon
NEG SEQ DIR OC1 TYPE
selecting this setting it must be kept in mind that the design uses a positive-sequence restraint technique.
NEG SEQ DIR OC1 REV LIMIT ANGLE: This setting defines a symmetrical (in both directions from the ECA) limit
angle for the reverse direction.
NEG SEQ DIR OC1 REV PICKUP: This setting defines the pickup level for the overcurrent unit in the reverse direc-
tion. Upon
NEG SEQ DIR OC1 TYPE
selecting this setting it must be kept in mind that the design uses a positive-sequence restraint technique.
5
Figure 5–93: NEGATIVE SEQUENCE DIRECTIONAL OC1 SCHEME LOGIC
5-198
selection, this pickup threshold applies to zero- or negative-sequence current. When
selection, this pickup threshold applies to zero- or negative-sequence current. When
D30 Line Distance Protection System
5 SETTINGS