Advertisement

5 SETTINGS
Two methods of resetting operation are available: "Timed" and "Instantaneous" (see the Inverse TOC Curve Characteristics
section for details on curve setup, trip times and reset operation). When the element is blocked, the time accumulator will
reset according to the reset characteristic. For example, if the element reset characteristic is set to "Instantaneous" and the
element is blocked, the time accumulator will be cleared immediately.
SETTING
NEUTRAL TOC1
FUNCTION:
Enabled = 1
SETTING
NEUTRAL TOC1
SOURCE:
IN
SETTING
NEUTRAL TOC1
BLOCK:
Off = 0
Figure 5–84: NEUTRAL TIME OVERCURRENT 1 SCHEME LOGIC
c) NEUTRAL INSTANTANEOUS OVERCURRENT (ANSI 50N, IEC PIOC)

PATH: SETTINGS
GROUPED ELEMENTS
 NEUTRAL IOC1
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
The neutral instantaneous overcurrent element may be used as an instantaneous function with no intentional delay or as a
definite time function. The element essentially responds to the magnitude of a neutral current fundamental frequency pha-
sor calculated from the phase currents. A positive-sequence restraint is applied for better performance. A small portion
(6.25%) of the positive-sequence current magnitude is subtracted from the zero-sequence current magnitude when forming
the operating quantity of the element as follows:
The positive-sequence restraint allows for more sensitive settings by counterbalancing spurious zero-sequence currents
resulting from
GE Multilin
SETTINGS
NEUTRAL TOC1
INPUT:
NEUTRAL TOC1
PICKUP:
NEUTRAL TOC1
CURVE:
NEUTRAL TOC1
TD MULTIPLIER:
NEUTRAL TOC 1
RESET:
AND
RUN
t

SETTING GROUP 1(6)
NEUTRAL IOC1
FUNCTION: Disabled
NEUTRAL IOC1 SIGNAL
SOURCE: SRC 1
NEUTRAL IOC1
PICKUP:
1.000 pu
NEUTRAL IOC1 PICKUP
DELAY:
0.00 s
NEUTRAL IOC1 RESET
DELAY:
0.00 s
NEUTRAL IOC1 BLOCK:
Off
NEUTRAL IOC1
TARGET: Self-reset
NEUTRAL IOC1
EVENTS: Disabled
I
3
×
(
I_0
Kx I_1
)
where K
=
op
D30 Line Distance Protection System
5.6 GROUPED ELEMENTS
FLEXLOGIC OPERANDS
NEUTRAL TOC1 PKP
NEUTRAL TOC1 DPO
IN
PICKUP
NEUTRAL TOC1 OP
I

NEUTRAL CURRENT
NEUTRAL IOC1(4)
Range: Disabled, Enabled
Range: SRC 1, SRC 2
Range: 0.000 to 30.000 pu in steps of 0.001
Range: 0.00 to 600.00 s in steps of 0.01
Range: 0.00 to 600.00 s in steps of 0.01
Range: FlexLogic operand
Range: Self-reset, Latched, Disabled
Range: Disabled, Enabled
1 16
=
827034A4.VSD
5
(EQ 5.15)
5-183