Set-Attr - Keywords And Values For All <Aids - Symmetricom TimeProvider 1100 Reference Manual

Edge clock tl1 reference guide
Hide thumbs Also See for TimeProvider 1100:
Table of Contents

Advertisement

Chapter 2 TL1 Command Syntax and Description
Set Attribute (SET-ATTR)
Table 2-32. SET-ATTR – Keywords and Values for all <aids>
<keyword>
<value>
BRDGTIM
300 to
(SYS aid
500000
only)
DISABLE
ELEVTIME
ENABLE
(SYS aid
only)
DISABLE
FACTORY
(none)
(SYS aid
only)
Alarm ID
NR
NA
MN
MJ
CR
Note: See
levels that can be set.
Refer to
Table B-1
and a brief description of each. The table also shows the possible alarm levels that
can be set with the SET-ATTR command, whether or not the error delay is editable,
and certain other defaults for each Alarm ID.
Example
To set the system-level EXPFAIL event's alarm level to critical:
Input
SET-ATTR::SYS:TP1000::EXPFAIL=CR;
Normal Response
TP-SSU 05-02-10 13:35:56
M
TP1000 COMPLD
;
Autonomous Message
TP-SSU 05-02-10 13:35:56
A
175 REPT EVT
"IMC,EQPT:ALMCHG,TC,05-02-10,13-35-56,,,,:\"ALARM PARAMETER HAS CHANGED,
EXPFAIL,CRITICAL\""
;
132 TimeProvider TL1 Reference Guide
In PRR mode, this sets the length of time, in seconds, the
system remains in bridging mode.
Disables the Bridging mode.
Minor alarms elevate to Major, and Major alarms elevate to
Critical after the system elevation time has elapsed.
Note: The system elevation time is 86400 seconds (24
hours), and cannot be changed.
The system does not automatically elevate alarms.
Sets the alarm level for all alarms to their factory settings.
The alarm level for the specified alarm is set as not-reported. N/A
The specified alarm is set as a non-alarm event.
The alarm level for the specified alarm is set to "minor."
The alarm level for the specified alarm is set to "major."
The alarm level for the specified alarm is set to "critical."
Table B-1
for a list of alarm identifiers, and possible alarm
for a list of all of the TimeProvider Alarm Identifiers (Alarm IDs)
Description
097-58001-01 Revision E – September 2006
Default
900
seconds
DISABLE
N/A