Channel Tests - GE L30 Instruction Manual

Line current differential system, ur series
Hide thumbs Also See for L30:
Table of Contents

Advertisement

6.2 STATUS
b) STATISTICS
PATH: ACTUAL VALUES
REMOTE DEVICE
Statistical data (two types) for up to 16 programmed remote devices is shown here.
The StNum number is obtained from the indicated remote device and is incremented whenever a change of state of at
least one DNA or UserSt bit occurs. The SqNum number is obtained from the indicated remote device and is incremented
whenever a GSSE message is sent. This number will rollover to zero when a count of 4 294 967 295 is incremented.
PATH: ACTUAL VALUES

CHANNEL TESTS

6
The status information for two channels is shown here. A brief description of each actual value is below:
6-6
STATUS
REMOTE DEVICES STATISTICS
1
REMOTE DEVICE
StNum:
REMOTE DEVICE
MESSAGE
SqNum:
STATUS
CHANNEL TESTS
CHANNEL 1
STATUS: n/a
CHANNEL 1 LOST
MESSAGE
PACKETS:
CHANNEL 1 LOCAL
MESSAGE
LOOPBCK STATUS: n/a
CHANNEL 1 REMOTE
MESSAGE
LOOPBCK STATUS: n/a
CHANNEL 1
MESSAGE
LOOP DELAY:
CHANNEL 1 ASYMMETRY:
MESSAGE
+0.0 ms
CHANNEL 2
MESSAGE
STATUS: n/a
CHANNEL 2 LOST
MESSAGE
PACKETS:
CHANNEL 2 LOCAL
MESSAGE
LOOPBCK STATUS: n/a
CHANNEL 2 REMOTE
MESSAGE
LOOPBCK STATUS: n/a
CHANNEL 2
MESSAGE
LOOP DELAY:
CHANNEL 2 ASYMMETRY:
MESSAGE
+0.0 ms
VALIDITY OF CHANNEL
MESSAGE
CONFIGURATION: n/a
PFLL
MESSAGE
STATUS: n/a
L30 Line Current Differential System
REMOTE DEVICE 1(16)
1
0
1
0
Range: n/a, FAIL, OK
Range: 0 to 65535 in steps of 1. Reset count to 0 through
the
COMMANDS
0
Range: n/a, FAIL, OK
Range: n/a, FAIL, OK
0.0 ms
Range: –10 to 10 ms in steps of 0.1
Range: n/a, FAIL, OK
Range: 0 to 65535 in steps of 1. Reset count to 0 through
the
COMMANDS
0
Range: n/a, FAIL, OK
Range: n/a, FAIL, OK
0.0 ms
Range: –10 to 10 ms in steps of 0.1
Range: n/a, FAIL, OK
Range: n/a, FAIL, OK
6 ACTUAL VALUES
6.2.10 CHANNEL TESTS
menu.
CLEAR RECORDS
CLEAR RECORDS
menu.