B.4 MEMORY MAPPING
F192
ENUMERATION: ETHERNET OPERATION MODE
0 = Half-Duplex, 1 = Full-Duplex
F194
ENUMERATION: DNP SCALE
B
0 = 0.01, 1 = 0.1, 2 = 1, 3 = 10, 4 = 100, 5 = 1000, 6 = 10000,
7 = 100000, 8 = 0.001
F199
ENUMERATION: DISABLED/ENABLED/CUSTOM
0 = Disabled, 1 = Enabled, 2 = Custom
F200
TEXT40: 40-CHARACTER ASCII TEXT
20 registers, 16 Bits: 1st Char MSB, 2nd Char. LSB
F201
TEXT8: 8-CHARACTER ASCII PASSCODE
4 registers, 16 Bits: 1st Char MSB, 2nd Char. LSB
F202
TEXT20: 20-CHARACTER ASCII TEXT
10 registers, 16 Bits: 1st Char MSB, 2nd Char. LSB
F203
TEXT16: 16-CHARACTER ASCII TEXT
F204
TEXT80: 80-CHARACTER ASCII TEXT
F205
TEXT12: 12-CHARACTER ASCII TEXT
F206
TEXT6: 6-CHARACTER ASCII TEXT
F207
TEXT4: 4-CHARACTER ASCII TEXT
F208
TEXT2: 2-CHARACTER ASCII TEXT
F211
ENUMERATION: SOURCE SELECTION
0 = None, 1 = SRC 1, 2 = SRC 2, 3 = SRC 3, 4 = SRC 4,
5 = SRC 5, 6 = SRC 6
B-70
F213
TEXT32: 32-CHARACTER ASCII TEXT
F220
ENUMERATION: PUSHBUTTON MESSAGE PRIORITY
value
0
1
2
F222
ENUMERATION: TEST ENUMERATION
0 = Test Enumeration 0, 1 = Test Enumeration 1
F223
ENUMERATION: DIAGNOSTIC TEST
0 = No Test, 1 = Run Test, 2 = End Test
F226
ENUMERATION: REMOTE INPUT/OUTPUT TRANSFER
METHOD
0 = None, 1 = GSSE, 2 = GOOSE
F227
ENUMERATION: RELAY SERVICE STATUS
0 = Unknown, 1 = Relay In Service, 2 = Relay Out Of Service
F232
ENUMERATION: CONFIGURABLE GOOSE DATASET ITEMS
FOR TRANSMISSION
value
0
1
2
3
4
↓
255
256
257
258
259
260
261
262
263
264
265
266
L30 Line Current Differential System
priority
Disabled
Normal
High Priority
GOOSE dataset item
None
GGIO1.ST.Ind1.q
GGIO1.ST.Ind1.stVal
GGIO1.ST.Ind2.q
GGIO1.ST.Ind2.stVal
↓
GGIO1.ST.Ind128.q
GGIO1.ST.Ind128.stVal
MMXU1.MX.TotW.mag.f
MMXU1.MX.TotVAr.mag.f
MMXU1.MX.TotVA.mag.f
MMXU1.MX.TotPF.mag.f
MMXU1.MX.Hz.mag.f
MMXU1.MX.PPV.phsAB.cVal.mag.f
MMXU1.MX.PPV.phsAB.cVal.ang.f
MMXU1.MX.PPV.phsBC.cVal.mag.f
MMXU1.MX.PPV.phsBC.cVal.ang.f
MMXU1.MX.PPV.phsCA.cVal.mag.f
APPENDIX B
GE Multilin