Trip Decision Example; Trip Decision Test - GE L30 Instruction Manual

Line current differential system, ur series
Hide thumbs Also See for L30:
Table of Contents

Advertisement

9.2 OPERATING CONDITION CHARACTERISTICS
Assume the following settings:
Slope 1: S
= 10%
1
Slope 2: S
= 10%
2
Breakpoint: BP = 5 pu secondary
Pickup: P = 0.5 pu
Assume the following local and remote currents:
Local current: I
local
Remote current: I
remote
The assumed condition is a radial line with a high resistance fault, with the source at the local end only, and through a resis-
tive load current. The operating current is:
Since the current at both ends is less than the breakpoint value of 5.0, the equation for two-terminal mode is used to calcu-
late restraint as follows.
σ
where
= 0, assuming a pure sine wave.
The trip condition is shown below.
The use of the
CURRENT DIFF PICKUP
settings are discussed in the Current differential section of chapter 5.
The following figure shows how the L30 settings affect the restraint characteristics. The local and remote currents are 180°
apart, which represents an external fault. The breakpoint between the two slopes indicates the point where the restraint
area is becoming wider to override uncertainties from CT saturation, fault noise, harmonics, etc. Increasing the slope per-
centage increases the width of the restraint area.
9
9-18
= 4.0 pu ∠0°
= 0.8 pu ∠180°
2
2
I
I_L
I_R
4.0 0°
=
+
=
op
2
2
2
(
)
(
I
2 S
I_L
=
+
Rest
1
2
2
(
(
)
)
=
2
0.1
4
+
=
0.8328
2
I
10.24
Op
>
----------- -
1
----------------- -
2
0.8328
I
Rest
,
CURRENT DIFF RESTRAINT 1
L30 Line Current Differential System
2
0.8 180°
10.24
+
=
2
2
2
)
σ
2 S
I_R
2P
+
+
1
2
2
2
(
(
)
)
(
)
2
0.1
0.8
+
2
0.5
>
12.3
1
Trip
=
,
CURRENT DIFF RESTRAINT 2
9 THEORY OF OPERATION

9.2.2 TRIP DECISION EXAMPLE

+
0

9.2.3 TRIP DECISION TEST

, and
CURRENT DIFF BREAK PT
GE Multilin
(EQ 9.34)
(EQ 9.35)
(EQ 9.36)

Advertisement

Table of Contents
loading

Table of Contents