5 SETTINGS
a) MAIN MENU
PATH: SETTINGS
GROUPED ELEMENTS

NEUTRAL CURRENT

MESSAGE
MESSAGE
MESSAGE
b) NEUTRAL TIME OVERCURRENT (ANSI 51N)
PATH: SETTINGS
GROUPED ELEMENTS
NEUTRAL TOC1
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
The neutral time overcurrent element can provide a desired time-delay operating characteristic versus the applied current
or be used as a simple definite time element. The neutral current input value is a quantity calculated as 3Io from the phase
currents and may be programmed as fundamental phasor magnitude or total waveform RMS magnitude as required by the
application.
GE Multilin
SETTING GROUP 1(6)
NEUTRAL CURRENT
NEUTRAL TOC1
NEUTRAL TOC2
NEUTRAL IOC1
NEUTRAL IOC2
SETTING GROUP 1(6)
NEUTRAL CURRENT
NEUTRAL TOC1
FUNCTION: Disabled
NEUTRAL TOC1 SIGNAL
SOURCE: SRC 1
NEUTRAL TOC1
INPUT: Phasor
NEUTRAL TOC1
PICKUP:
1.000 pu
NEUTRAL TOC1
CURVE: IEEE Mod Inv
NEUTRAL TOC1
TD MULTIPLIER:
1.00
NEUTRAL TOC1
RESET: Instantaneous
NEUTRAL TOC1 BLOCK:
Off
NEUTRAL TOC1
TARGET: Self-reset
NEUTRAL TOC1
EVENTS: Disabled
L30 Line Current Differential System
5.6 GROUPED ELEMENTS
5.6.5 NEUTRAL CURRENT
See page 5-131.
See page 5-131.
See page 5-132.
See page 5-132.
NEUTRAL TOC1(2)
Range: Disabled, Enabled
Range: SRC 1, SRC 2
Range: Phasor, RMS
Range: 0.000 to 30.000 pu in steps of 0.001
Range: See OVERCURRENT CURVE TYPES table
Range: 0.00 to 600.00 in steps of 0.01
Range: Instantaneous, Timed
Range: FlexLogic™ operand
Range: Self-reset, Latched, Disabled
Range: Disabled, Enabled