5 SETTINGS
e) PMU TRIGGERING OVERVIEW
PATH: SETTINGS
SYSTEM SETUP
PMU 1
TRIGGERING
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
Each logical phasor measurement unit (PMU) contains five triggering mechanisms to facilitate triggering of the associated
PMU recorder, or cross-triggering of other PMUs of the system. They are:
Overfrequency and underfrequency.
Overvoltage and undervoltage.
Overcurrent.
Overpower.
High rate of change of frequency.
The pre-configured triggers could be augmented with a user-specified condition built freely using programmable logic of the
relay. The entire triggering logic is refreshed once every two power system cycles.
All five triggering functions and the user-definable condition are consolidated (ORed) and connected to the PMU recorder.
Each trigger can be programmed to log its operation into the event recorder, and to signal its operation via targets. The five
triggers drive the STAT bits of the data frame to inform the destination of the synchrophasor data regarding the cause of
trigger. The following convention is adopted to drive bits 11, 3, 2, 1, and 0 of the STAT word.
SETTING
PMU 1 USER TRIGGER:
Off = 0
FLEXLOGIC OPERANDS
PMU 1 FREQ TRIGGER
PMU 1 ROCOF TRIGGER
PMU 1 VOLT TRIGGER
PMU 1 CURR TRIGGER
PMU 1 POWER TRIGGER
f) USER TRIGGERING
PATH: SETTINGS
SYSTEM SETUP
PMU 1 USER
TRIGGER
The user trigger allows customized triggering logic to be constructed from FlexLogic™. The entire triggering logic is
refreshed once every two power system cycles.
GE Multilin
PHASOR...
PHASOR MEASUREMENT UNIT 1
PMU 1 USER
TRIGGER
PMU 1 FREQUENCY
TRIGGER
PMU 1 VOLTAGE
TRIGGER
PMU 1 CURRENT
TRIGGER
PMU 1 POWER
TRIGGER
PMU 1 df/dt
TRIGGER
bit 0
bit 3, bit 11
bit 1
bit 2
Figure 5–30: STAT BITS LOGIC
PHASOR MEASUREMENT...
PMU1 USER TRIGGER:
Off
L30 Line Current Differential System
PMU 1 TRIGGERING
See page 5-85.
See page 5-86.
See page 5-87.
See page 5-88.
See page 5-89.
See page 5-91.
FLEXLOGIC OPERAND
PMU 1 TRIGGERED
PMU 1 recorder
847004A1.CDR
PMU 1 TRIGGERING
PMU 1 USER TRIGGER
Range: FlexLogic™ operands
5.4 SYSTEM SETUP