5 SETTINGS
PATH: SETTINGS
PRODUCT SETUP
DNP NETWORK
CLIENT ADDRESSES
MESSAGE
MESSAGE
MESSAGE
MESSAGE
The
DNP UNSOL RESPONSE FUNCTION
mechanism. The
DNP UNSOL RESPONSE TIMEOUT
response. The
DNP UNSOL RESPONSE MAX RETRIES
ited response without receiving confirmation from the master; a value of "255" allows infinite re-tries. The
is the DNP address to which all unsolicited responses are sent. The IP address to which unsolic-
RESPONSE DEST ADDRESS
ited responses are sent is determined by the L30 from the current TCP connection or the most recent UDP message.
The DNP scale factor settings are numbers used to scale analog input point values. These settings group the L30 analog
input data into the following types: current, voltage, power, energy, power factor, and other. Each setting represents the
scale factor for all analog input points of that type. For example, if the
all DNP analog input points that are voltages will be returned with values 1000 times smaller (for example, a value of 72000
V on the L30 will be returned as 72). These settings are useful when analog input values must be adjusted to fit within cer-
tain ranges in DNP masters. Note that a scale factor of 0.1 is equivalent to a multiplier of 10 (that is, the value will be 10
times larger).
The
DNP DEFAULT DEADBAND
settings group the L30 analog input data into the following types: current, voltage, power, energy, power factor, and other.
Each setting represents the default deadband value for all analog input points of that type. For example, to trigger unsolic-
ited responses from the L30 when any current values change by 15 A, the
be set to "15". Note that these settings are the deadband default values. DNP object 34 points can be used to change dead-
band values, from the default, for each individual DNP analog input point. Whenever power is removed and re-applied to
the L30, the default deadbands will be in effect.
The L30 relay does not support energy metering. As such, the
settings are not applicable.
DEFAULT DEADBAND
NOTE
The
DNP TIME SYNC IIN PERIOD
Changing this time allows the DNP master to send time synchronization commands more or less often, as required.
The
DNP MESSAGE FRAGMENT SIZE
fragment sizes allow for more efficient throughput; smaller fragment sizes cause more application layer confirmations to be
necessary which can provide for more robust data transfer over noisy communication channels.
When the DNP data points (analog inputs and/or binary inputs) are configured for Ethernet-enabled relays,
check the "DNP Points Lists" L30 web page to view the points lists. This page can be viewed with a web
NOTE
browser by entering the L30 IP address to access the L30 "Main Menu", then by selecting the "Device Infor-
mation Menu" > "DNP Points Lists" menu item.
The
DNP OBJECT 1 DEFAULT VARIATION
default variation number for object types 1, 2, 20, 21, 22, 23, 30, and 32. The default variation refers to the variation
response when variation 0 is requested and/or in class 0, 1, 2, or 3 scans. Refer to the DNP implementation section in
appendix E for additional details.
The DNP binary outputs typically map one-to-one to IED data points. That is, each DNP binary output controls a single
physical or virtual control point in an IED. In the L30 relay, DNP binary outputs are mapped to virtual inputs. However, some
legacy DNP implementations use a mapping of one DNP binary output to two physical or virtual control points to support
the concept of trip/close (for circuit breakers) or raise/lower (for tap changers) using a single control point. That is, the DNP
GE Multilin
COMMUNICATIONS
CLIENT ADDRESS 1:
0.0.0.0
CLIENT ADDRESS 2:
0.0.0.0
CLIENT ADDRESS 3:
0.0.0.0
CLIENT ADDRESS 4:
0.0.0.0
CLIENT ADDRESS 5:
0.0.0.0
should be "Disabled" for RS485 applications since there is no collision avoidance
sets the time the L30 waits for a DNP master to confirm an unsolicited
setting determines the number of times the L30 retransmits an unsolic-
settings determine when to trigger unsolicited responses containing analog input data. These
setting determines how often the Need Time Internal Indication (IIN) bit is set by the L30.
setting determines the size, in bytes, at which message fragmentation occurs. Large
to
DNP OBJECT 32 DEFAULT VARIATION
L30 Line Current Differential System
DNP PROTOCOL
DNP NETWORK CLIENT ADDRESSES
Range: standard IP address
Range: standard IP address
Range: standard IP address
Range: standard IP address
Range: standard IP address
DNP VOLTAGE SCALE FACTOR
DNP CURRENT DEFAULT DEADBAND
DNP ENERGY SCALE FACTOR
settings allow the user to select the DNP
5.2 PRODUCT SETUP
DNP UNSOL
setting is set to "1000",