5.6 GROUPED ELEMENTS
PATH: SETTINGS
GROUPED ELEMENTS

BREAKER FAILURE 1

5
5-138
SETTING GROUP 1(6)
BF1 FUNCTION:
Disabled
BF1 MODE:
MESSAGE
3-Pole
BF1 SOURCE:
MESSAGE
SRC 1
BF1 USE AMP SUPV:
MESSAGE
Yes
BF1 USE SEAL-IN:
MESSAGE
Yes
BF1 3-POLE INITIATE:
MESSAGE
Off
BF1 BLOCK:
MESSAGE
Off
BF1 PH AMP SUPV
MESSAGE
PICKUP: 1.050 pu
BF1 N AMP SUPV
MESSAGE
PICKUP: 1.050 pu
BF1 USE TIMER 1:
MESSAGE
Yes
BF1 TIMER 1 PICKUP
MESSAGE
DELAY: 0.000 s
BF1 USE TIMER 2:
MESSAGE
Yes
BF1 TIMER 2 PICKUP
MESSAGE
DELAY: 0.000 s
BF1 USE TIMER 3:
MESSAGE
Yes
BF1 TIMER 3 PICKUP
MESSAGE
DELAY: 0.000 s
BF1 BKR POS1 φA/3P:
MESSAGE
Off
BF1 BKR POS2 φA/3P:
MESSAGE
Off
BF1 BREAKER TEST ON:
MESSAGE
Off
BF1 PH AMP HISET
MESSAGE
PICKUP: 1.050 pu
BF1 N AMP HISET
MESSAGE
PICKUP: 1.050 pu
BF1 PH AMP LOSET
MESSAGE
PICKUP: 1.050 pu
L30 Line Current Differential System
5.6.8 BREAKER FAILURE
BREAKER FAILURE
BREAKER FAILURE 1(2)
Range: Disabled, Enabled
Range: 3-Pole, 1-Pole
Range: SRC 1, SRC 2
Range: Yes, No
Range: Yes, No
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: 0.001 to 30.000 pu in steps of 0.001
Range: 0.001 to 30.000 pu in steps of 0.001
Range: Yes, No
Range: 0.000 to 65.535 s in steps of 0.001
Range: Yes, No
Range: 0.000 to 65.535 s in steps of 0.001
Range: Yes, No
Range: 0.000 to 65.535 s in steps of 0.001
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: 0.001 to 30.000 pu in steps of 0.001
Range: 0.001 to 30.000 pu in steps of 0.001
Range: 0.001 to 30.000 pu in steps of 0.001
5 SETTINGS
GE Multilin