GE L30 Instruction Manual page 303

Line current differential system, ur series
Hide thumbs Also See for L30:
Table of Contents

Advertisement

5 SETTINGS
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
GE Multilin
AR1 INITIATE:
Off
AR1 BLOCK:
Off
AR1 MAX NUMBER OF
SHOTS: 1
AR1 REDUCE MAX TO 1:
Off
AR1 REDUCE MAX TO 2:
Off
AR1 REDUCE MAX TO 3:
Off
AR1 MANUAL CLOSE:
Off
AR1 MNL RST FRM LO:
Off
AR1 RESET LOCKOUT IF
BREAKER CLOSED: Off
AR1 RESET LOCKOUT ON
MANUAL CLOSE: Off
AR1 BKR CLOSED:
Off
AR1 BKR OPEN:
Off
AR1 BLK TIME UPON
MNL CLS: 10.000 s
AR1 DEAD TIME 1:
1.000 s
AR1 DEAD TIME 2:
2.000 s
AR1 DEAD TIME 3:
3.000 s
AR1 DEAD TIME 4:
4.000 s
AR1 ADD DELAY 1:
Off
AR1 DELAY 1:
0.000 s
AR1 ADD DELAY 2:
Off
AR1 DELAY 2:
0.000 s
AR1 RESET LOCKOUT
DELAY: 60.000
L30 Line Current Differential System
5.7 CONTROL ELEMENTS
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: 1, 2, 3, 4
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: Off, On
Range: Off, On
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: 0.00 to 655.35 s in steps of 0.01
Range: 0.00 to 655.35 s in steps of 0.01
Range: 0.00 to 655.35 s in steps of 0.01
Range: 0.00 to 655.35 s in steps of 0.01
Range: 0.00 to 655.35 s in steps of 0.01
Range: FlexLogic™ operand
Range: 0.00 to 655.35 s in steps of 0.01
Range: FlexLogic™ operand
Range: 0.00 to 655.35 s in steps of 0.01
Range: 0.00 to 655.35 s in steps of 0.01
5
5-167