GE L30 Instruction Manual page 461

Line current differential system, ur series
Hide thumbs Also See for L30:
Table of Contents

Advertisement

APPENDIX B
Table B–9: MODBUS MEMORY MAP (Sheet 11 of 52)
ADDR
REGISTER NAME
3508
RTD Input 25 Value
3509
RTD Input 26 Value
350A
RTD Input 27 Value
350B
RTD Input 28 Value
350C
RTD Input 29 Value
350D
RTD Input 30 Value
350E
RTD Input 31 Value
350F
RTD Input 32 Value
3510
RTD Input 33 Value
3511
RTD Input 34 Value
3512
RTD Input 35 Value
3513
RTD Input 36 Value
3514
RTD Input 37 Value
3515
RTD Input 38 Value
3516
RTD Input 39 Value
3517
RTD Input 40 Value
3518
RTD Input 41 Value
3519
RTD Input 42 Value
351A
RTD Input 43 Value
351B
RTD Input 44 Value
351C
RTD Input 45 Value
351D
RTD Input 46 Value
351E
RTD Input 47 Value
351F
RTD Input 48 Value
Passwords (Read/Write Command)
4000
Command Password Setting
Passwords (Read/Write Setting)
4002
Setting Password Setting
Passwords (Read/Write)
4008
Command Password Entry
400A
Setting Password Entry
Passwords (read only actual values)
4010
Command password status
4011
Setting password status
Passwords (read/write settings)
4012
Control password access timeout
4013
Setting password access timeout
4014
Invalid password attempts
4015
Password lockout duration
4016
Password access events
4017
Local setting authorization
4018
Remote setting authorization
4019
Access authorization timeout
User Display Invoke (Read/Write Setting)
4040
Invoke and Scroll Through User Display Menu Operand
LED Test (Read/Write Setting)
4048
LED Test Function
4049
LED Test Control
Preferences (Read/Write Setting)
404F
Language
4050
Flash Message Time
4051
Default Message Timeout
4052
Default Message Intensity
4053
Screen Saver Feature
GE Multilin
RANGE
-32768 to 32767
-32768 to 32767
-32768 to 32767
-32768 to 32767
-32768 to 32767
-32768 to 32767
-32768 to 32767
-32768 to 32767
-32768 to 32767
-32768 to 32767
-32768 to 32767
-32768 to 32767
-32768 to 32767
-32768 to 32767
-32768 to 32767
-32768 to 32767
-32768 to 32767
-32768 to 32767
-32768 to 32767
-32768 to 32767
-32768 to 32767
-32768 to 32767
-32768 to 32767
-32768 to 32767
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 1
0 to 1
5 to 480
5 to 480
2 to 5
5 to 60
0 to 1
1 to 65535
0 to 65535
5 to 480
0 to 65535
0 to 1
0 to 65535
0 to 3
0.5 to 10
10 to 900
0 to 3
0 to 1
L30 Line Current Differential System
B.4 MEMORY MAPPING
UNITS
STEP
FORMAT
°C
1
F002
°C
1
F002
°C
1
F002
°C
1
F002
°C
1
F002
°C
1
F002
°C
1
F002
°C
1
F002
°C
1
F002
°C
1
F002
°C
1
F002
°C
1
F002
°C
1
F002
°C
1
F002
°C
1
F002
°C
1
F002
°C
1
F002
°C
1
F002
°C
1
F002
°C
1
F002
°C
1
F002
°C
1
F002
°C
1
F002
°C
1
F002
---
1
F003
---
1
F003
---
1
F003
---
1
F003
---
1
F102
---
1
F102
minutes
1
F001
minutes
1
F001
---
1
F001
minutes
1
F001
---
1
F102
---
1
F300
---
1
F300
minutes
1
F001
---
1
F300
---
1
F102
---
1
F300
---
1
F531
s
0.1
F001
s
1
F001
---
1
F101
---
1
F102
DEFAULT
0
0
0
0
0
B
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0 (Disabled)
0 (Disabled)
5
30
3
5
0 (Disabled)
1
1
30
0
0 (Disabled)
0
0 (English)
10
300
0 (25%)
0 (Disabled)
B-19

Advertisement

Table of Contents
loading

Table of Contents