GE L30 Instruction Manual page 225

Line current differential system, ur series
Hide thumbs Also See for L30:
Table of Contents

Advertisement

5 SETTINGS
SETTINGS
PMU 1 CURR TRIGGER
FUNCTION:
Enabled = 1
PMU 1 CURR TRIG BLK:
Off = 0
SETTINGS
PMU 1 SIGNAL
SOURCE:
IA
IB
IC
j) POWER TRIGGERING
PATH: SETTINGS
SYSTEM SETUP
PMU 1 POWER
TRIGGER
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
This element responds to abnormal power. Separate thresholds are provided for active, reactive, and apparent powers. In
terms of signaling its operation the element does not differentiate between the three types of power. The trigger responds to
the single-phase and three-phase power signals of the phasor measurement unit (PMU) source.
PMU 1 POWER TRIGGER ACTIVE: This setting specifies the pickup threshold for the active power of the source. For
single-phase power, 1 pu is a product of 1 pu voltage and 1 pu current, or the product of nominal secondary voltage,
the VT ratio and the nominal primary current. For the three-phase power, 1 pu is three times that for a single-phase
power. The comparator applies a 3% hysteresis.
PMU 1 POWER TRIGGER REACTIVE: This setting specifies the pickup threshold for the reactive power of the
source. For single-phase power, 1 pu is a product of 1 pu voltage and 1 pu current, or the product of nominal second-
ary voltage, the VT ratio and the nominal primary current. For the three-phase power, 1 pu is three times that for a sin-
gle-phase power. The comparator applies a 3% hysteresis.
GE Multilin
SETTINGS
PMU 1 CURR TRIGGER PICKUP:
RUN
I > PICKUP
I > PICKUP
I > PICKUP
Figure 5–33: CURRENT TRIGGER SCHEME LOGIC
PHASOR MEASUREMENT...
PMU 1 POWER TRIGGER
FUNCTION: Disabled
PMU 1 POWER TRIGGER
ACTIVE: 1.250 pu
PMU 1 POWER TRIGGER
REACTIVE: 1.250 pu
PMU 1 POWER TRIGGER
APPARENT: 1.250 pu
PMU 1 POWER TRIGGER
PKP TIME: 0.10 s
PMU 1 POWER TRIGGER
DPO TIME: 1.00 s
PMU 1 PWR TRIG BLK:
Off
PMU 1 POWER TRIGGER
TARGET: Self-Reset
PMU 1 POWER TRIGGER
EVENTS: Disabled
L30 Line Current Differential System
FLEXLOGIC OPERANDS
PMU 1 FREQ TRIGGER
PMU 1 VOLT TRIGGER
PMU 1 POWER TRIGGER
PMU 1 ROCOF TRIGGER
SETTING
PMU 1 USER TRIGGER:
Off = 0
SETTINGS
to STAT bits of
PMU 1 CURR TRIGGER PKP TIME:
the data frame
PMU 1 CURR TRIGGER DPO TIME:
t
PKP
t
DPO
PMU 1 TRIGGERING
PMU 1 POWER TRIGGER
Range: Enabled, Disabled
Range: 0.250 to 3.000 pu in steps of 0.001
Range: 0.250 to 3.000 pu in steps of 0.001
Range: 0.250 to 3.000 pu in steps of 0.001
Range: 0.00 to 600.00 s in steps of 0.01
Range: 0.00 to 600.00 s in steps of 0.01
Range: FlexLogic™ operand
Range: Self-Reset, Latched, Disabled
Range: Enabled, Disabled
5.4 SYSTEM SETUP
FLEXLOGIC OPERAND
PMU 1 TRIGGERED
FLEXLOGIC OPERAND
PMU 1 CURR TRIGGER
847000A1.CDR
5
5-89

Advertisement

Table of Contents
loading

Table of Contents