B.4 MEMORY MAPPING
Table B–9: MODBUS MEMORY MAP (Sheet 50 of 52)
ADDR
REGISTER NAME
EA4D
PMU Network Reporting ID Code
EA4E
PMU Network Reporting Rate
EA4F
PMU Network Reporting Style
EA50
PMU Network Reporting Format
EA51
PMU Network PDC Control
B
EA52
PMU TCP port number
EA53
PMU UDP port number 1
EA54
PMU UDP port number 2
Phasor Measurement Unit Basic Configuration (Read/Write Setting)
EA58
PMU 1 Function
EA59
PMU 1 IDcode
EA5A
PMU 1 STN
EA62
PMU 1 Source
EA63
PMU 1 Post-Filter
Phasor Measurement Unit Calibration (Read/Write Setting)
EA88
PMU 1 Va Calibration Angle
EA89
PMU 1 Vb Calibration Angle
EA8A
PMU 1 Vc Calibration Angle
EA8B
PMU 1 Vx Calibration Angle
EA8C
PMU 1 Ia Calibration Angle
EA8D
PMU 1 Ib Calibration Angle
EA8E
PMU 1 Ic Calibration Angle
EA8F
PMU 1 Ig Calibration Angle
EA90
PMU 1 Sequence Voltage Shift Angle
EA91
PMU 1 Sequence Current Shift Angle
Phasor Measurement Unit Triggering (Read/Write Setting)
EAB0
PMU 1 User Trigger
Phasor Measurement Unit Current Trigger (Read/Write Setting)
EAB4
PMU 1 Current Trigger Function
EAB5
PMU 1 Current Trigger Pickup
EAB6
PMU 1 Current Trigger Pickup Time
EAB7
PMU 1 Current Trigger Dropout Time
EAB8
PMU 1 Current Trigger Block (3 items)
EABB
PMU 1 Current Trigger Target
EABC
PMU 1 Current Trigger Events
Phasor Measurement Unit df/dt Trigger (Read/Write Setting)
EAD8
PMU 1 df/dt Trigger Function
EAD9
PMU 1 df/dt Trigger Raise
EADA
PMU 1 df/dt Trigger Fall
EADB
PMU 1 df/dt Trigger Pickup Time
EADC
PMU 1 df/dt Trigger Dropout Time
EADD
PMU 1 df/dt Trigger Block (3 items)
EAE0
PMU 1 df/dt Trigger Target
EAE1
PMU 1 df/dt Trigger Events
Phasor Measurement Unit Frequency Trigger (Read/Write Setting)
EB00
PMU 1 Frequency Trigger Function
EB01
PMU 1 Frequency Trigger Low Frequency
EB02
PMU 1 Frequency Trigger High Frequency
EB03
PMU 1 Frequency Trigger Pickup Time
EB04
PMU 1 Frequency Trigger Dropout Time
EB05
PMU 1 Frequency Trigger Block (3 items)
EB08
PMU 1 Frequency Trigger Target
EB09
PMU 1 Frequency Trigger Events
B-58
RANGE
1 to 65534
0 to 11
0 to 1
0 to 1
0 to 1
1 to 65535
1 to 65535
1 to 65535
0 to 1
1 to 65534
---
0 to 5
0 to 3
-5 to 5
-5 to 5
-5 to 5
-5 to 5
-5 to 5
-5 to 5
-5 to 5
-5 to 5
-180 to 180
-180 to 180
0 to 65535
0 to 1
0.1 to 30
0 to 600
0 to 600
0 to 65535
0 to 2
0 to 1
0 to 1
0.1 to 15
0.1 to 15
0 to 600
0 to 600
0 to 65535
0 to 2
0 to 1
0 to 1
20 to 70
20 to 70
0 to 600
0 to 600
0 to 65535
0 to 2
0 to 1
L30 Line Current Differential System
APPENDIX B
UNITS
STEP
FORMAT
---
1
F001
---
1
F544
---
1
F546
---
1
F547
---
1
F102
---
1
F001
---
1
F001
---
1
F001
---
1
F102
---
1
F001
---
---
F203
---
1
F167
---
1
F540
1 (Symm-3-point)
°
0.05
F002
°
0.05
F002
°
0.05
F002
°
0.05
F002
°
0.05
F002
°
0.05
F002
°
0.05
F002
°
0.05
F002
°
30
F002
°
30
F002
---
1
F300
---
1
F102
pu
0.001
F001
s
0.01
F001
s
0.01
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F102
Hz/s
0.01
F001
Hz/s
0.01
F001
s
0.01
F001
s
0.01
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F102
Hz
0.01
F001
Hz
0.01
F001
s
0.01
F001
s
0.01
F001
---
1
F300
---
1
F109
---
1
F102
DEFAULT
1
3 (10/sec.)
0 (Polar)
0 (Integer)
0 (Disabled)
4712
4713
4714
0 (Disabled)
1
"GE-UR-PMU"
0 (SRC 1)
0
0
0
0
0
0
0
0
0
0
0
0 (Disabled)
1800
10
100
0
0 (Self-reset)
0 (Disabled)
0 (Disabled)
25
25
10
100
0
0 (Self-reset)
0 (Disabled)
0 (Disabled)
4900
6100
10
100
0
0 (Self-reset)
0 (Disabled)
GE Multilin