Hardware Functional Tests; Output Current Accuracy; Phase Voltage Input Accuracy - GE 489 Instruction Manual

Generator management relay
Hide thumbs Also See for 489:
Table of Contents

Advertisement

7 TESTING

7.2HARDWARE FUNCTIONAL TESTS

The specification for output and neutral end current input is ±0.5% of 2 × CT when the injected current is less than 2 × CT.
Perform the steps below to verify accuracy.
1.
Alter the following setpoint:
S2 SYSTEM SETUP
CURRENT SENSING
Measured values should be ±10 A. Inject the values shown in the table below and verify accuracy of the measured val-
2.
ues. View the measured values in:
A2 METERING DATA
CURRENT METERING
INJECTED CURRENT
1 A UNIT
5 A UNIT
0.1 A
0.5 A
0.2 A
1.0 A
0.5 A
2.5 A
1 A
1.5 A
7.5 A
2 A
10 A
The specification for phase voltage input accuracy is ±0.5% of full scale (200 V). Perform the steps below to verify accu-
racy.
1.
Alter the following setpoints:
S2 SYSTEM SETUP
VOLTAGE SENSING
S2 SYSTEM SETUP
VOLTAGE SENSING
Measured values should be ±1.0 V. Apply the voltage values shown in the table and verify accuracy of the measured
2.
values. View the measured values in:
A2 METERING DATA
VOLTAGE METERING
APPLIED LINE-
EXPECTED VOLTAGE
NEUTRAL VOLTAGE
30 V
50 V
100 V
150 V
200 V
270 V
GE Multilin
PHASE CT PRIMARY:
EXPECTED
CURRENT
100 A
200 A
500 A
5 A
1000 A
1500 A
2000 A
VT CONNECTION TYPE:
VOLTAGE TRANSFORMER RATIO:
READING
300 V
500 V
1000 V
1500 V
2000 V
2700 V
489 Generator Management Relay
7.2 HARDWARE FUNCTIONAL TESTS

7.2.1 OUTPUT CURRENT ACCURACY

"1000 A"
MEASURED CURRENT
PHASE A
PHASE B

7.2.2 PHASE VOLTAGE INPUT ACCURACY

"Wye"
"10.00:1"
MEASURED VOLTAGE
A-N
B-N
PHASE C
7
C-N
7-3