5.2 PRODUCT SETUP
master can operate a single point for both trip and close, or raise and lower, operations. The L30 can be configured to sup-
port paired control points, with each paired control point operating two virtual inputs. The
setting allows configuration of from 0 to 32 binary output paired controls. Points not configured as paired operate on
POINTS
a one-to-one basis.
The
setting is the DNP slave address. This number identifies the L30 on a DNP communications link. Each
DNP ADDRESS
DNP slave should be assigned a unique address.
The
DNP TCP CONNECTION TIMEOUT
there is no data traffic on a DNP TCP connection for greater than the time specified by this setting, the connection will be
aborted by the L30. This frees up the connection to be re-used by a client.
Relay power must be re-cycled after changing the
effect.
NOTE
f) DNP / IEC 60870-5-104 POINT LISTS
PATH: SETTINGS
PRODUCT SETUP
DNP / IEC104
POINT LISTS
The binary and analog inputs points for the DNP protocol, or the MSP and MME points for IEC 60870-5-104 protocol, can
configured to a maximum of 256 points. The value for each point is user-programmable and can be configured by assigning
FlexLogic™ operands for binary inputs / MSP points or FlexAnalog parameters for analog inputs / MME points.
5
The menu for the binary input points (DNP) or MSP points (IEC 60870-5-104) is shown below.
PATH: SETTINGS
PRODUCT SETUP
BINARY INPUT / MSP
POINTS
Up to 256 binary input points can be configured for the DNP or IEC 60870-5-104 protocols. The points are configured by
assigning an appropriate FlexLogic™ operand. Refer to the Introduction to FlexLogic™ section in this chapter for the full
range of assignable operands.
The menu for the analog input points (DNP) or MME points (IEC 60870-5-104) is shown below.
PATH: SETTINGS
PRODUCT SETUP
ANALOG INPUT / MME
POINTS
Up to 256 analog input points can be configured for the DNP or IEC 60870-5-104 protocols. The analog point list is config-
ured by assigning an appropriate FlexAnalog parameter to each point. Refer to Appendix A: FlexAnalog Parameters for the
full range of assignable parameters.
5-20
setting specifies a time delay for the detection of dead network TCP connections. If
COMMUNICATIONS
BINARY INPUT / MSP
POINTS
ANALOG INPUT / MME
MESSAGE
POINTS
COMMUNICATIONS
Point:
Off
Point:
MESSAGE
Off
Point:
MESSAGE
Off
COMMUNICATIONS
Point:
Off
Point:
MESSAGE
Off
Point:
MESSAGE
Off
L30 Line Current Differential System
DNP TCP CONNECTION TIMEOUT
DNP / IEC104 POINT LISTS
Range: see sub-menu below
Range: see sub-menu below
DNP / IEC104 POINT LISTS
Range: FlexLogic™ operand
0
Range: FlexLogic™ operand
1
Range: FlexLogic™ operand
255
DNP / IEC104 POINT LISTS
Range: any FlexAnalog parameter
0
Range: any FlexAnalog parameter
1
Range: any FlexAnalog parameter
255
5 SETTINGS
DNP NUMBER OF PAIRED CONTROL
setting for the changes to take
BINARY INPUT / MSP POINTS
ANALOG INPUT / MME POINTS
GE Multilin