GE L30 Instruction Manual page 240

Line current differential system, ur series
Hide thumbs Also See for L30:
Table of Contents

Advertisement

5.5 FLEXLOGIC™
Table 5–8: L30 FLEXLOGIC™ OPERANDS (Sheet 7 of 7)
OPERAND TYPE
OPERAND SYNTAX
USER-
PUSHBUTTON 1 ON
PROGRAMMABLE
PUSHBUTTON 1 OFF
PUSHBUTTONS
ANY PB ON
PUSHBUTTON 2 to 12
Some operands can be re-named by the user. These are the names of the breakers in the breaker control feature, the ID
(identification) of contact inputs, the ID of virtual inputs, and the ID of virtual outputs. If the user changes the default name
or ID of any of these operands, the assigned name will appear in the relay list of operands. The default names are shown in
the FlexLogic™ operands table above.
The characteristics of the logic gates are tabulated below, and the operators available in FlexLogic™ are listed in the Flex-
Logic™ operators table.
Table 5–9: FLEXLOGIC™ GATE CHARACTERISTICS
GATES
NUMBER OF INPUTS
NOT
OR
AND
NOR
NAND
XOR
5
5-104
OPERAND DESCRIPTION
Pushbutton number 1 is in the "On" position
Pushbutton number 1 is in the "Off" position
Any of twelve pushbuttons is in the "On" position
Same set of operands as PUSHBUTTON 1
OUTPUT IS '1' (= ON) IF...
1
input is '0'
2 to 16
any input is '1'
2 to 16
all inputs are '1'
2 to 16
all inputs are '0'
2 to 16
any input is '0'
2
only one input is '1'
L30 Line Current Differential System
5 SETTINGS
GE Multilin

Advertisement

Table of Contents
loading

Table of Contents