5 SETTINGS
Table 5–8: L30 FLEXLOGIC™ OPERANDS (Sheet 6 of 7)
OPERAND TYPE
OPERAND SYNTAX
LED INDICATORS:
LED IN SERVICE
Fixed front panel
LED TROUBLE
LEDs
LED TEST MODE
LED TRIP
LED ALARM
LED PICKUP
LED VOLTAGE
LED CURRENT
LED FREQUENCY
LED OTHER
LED PHASE A
LED PHASE B
LED PHASE C
LED NEUTRAL/GROUND
LED INDICATORS:
LED TEST IN PROGRESS
LED test
LED INDICATORS:
LED USER 1
User-programmable
LED USER 2 to 48
LEDs
PASSWORD
ACCESS LOC SETG OFF
SECURITY
ACCESS LOC SETG ON
ACCESS LOC CMND OFF
ACCESS LOC CMND ON
ACCESS REM SETG OFF
ACCESS REM SETG ON
ACCESS REM CMND OFF
ACCESS REM CMND ON
UNAUTHORIZED ACCESS
REMOTE DEVICES
REMOTE DEVICE 1 On
REMOTE DEVICE 16 On
REMOTE DEVICE 1 Off
REMOTE DEVICE 16 Off
RESETTING
RESET OP
RESET OP (COMMS)
RESET OP (OPERAND)
RESET OP (PUSHBUTTON)
SELF-
ANY MAJOR ERROR
DIAGNOSTICS
ANY MINOR ERROR
ANY SELF-TESTS
BATTERY FAIL
DIRECT DEVICE OFF
DIRECT RING BREAK
EQUIPMENT MISMATCH
ETHERNET SWITCH FAIL
FLEXLOGIC ERR TOKEN
IRIG-B FAILURE
LATCHING OUT ERROR
MAINTENANCE ALERT
PORT 1 OFFLINE
PORT 2 OFFLINE
PORT 3 OFFLINE
PORT 4 OFFLINE
PORT 5 OFFLINE
PORT 6 OFFLINE
PRI ETHERNET FAIL
PROCESS BUS FAILURE
REMOTE DEVICE OFF
RRTD COMM FAIL
SEC ETHERNET FAIL
SNTP FAILURE
SYSTEM EXCEPTION
TEMP MONITOR
UNIT NOT PROGRAMMED
TEMPERATURE
TEMP MONITOR
MONITOR
GE Multilin
OPERAND DESCRIPTION
Asserted when the front panel IN SERVICE LED is on.
Asserted when the front panel TROUBLE LED is on.
Asserted when the front panel TEST MODE LED is on.
Asserted when the front panel TRIP LED is on.
Asserted when the front panel ALARM LED is on.
Asserted when the front panel PICKUP LED is on.
Asserted when the front panel VOLTAGE LED is on.
Asserted when the front panel CURRENT LED is on.
Asserted when the front panel FREQUENCY LED is on.
Asserted when the front panel OTHER LED is on.
Asserted when the front panel PHASE A LED is on.
Asserted when the front panel PHASE B LED is on.
Asserted when the front panel PHASE C LED is on.
Asserted when the front panel NEUTRAL/GROUND LED is on.
An LED test has been initiated and has not finished.
Asserted when user-programmable LED 1 is on.
The operand above is available for user-programmable LEDs 2 through 48.
Asserted when local setting access is disabled.
Asserted when local setting access is enabled.
Asserted when local command access is disabled.
Asserted when local command access is enabled.
Asserted when remote setting access is disabled.
Asserted when remote setting access is enabled.
Asserted when remote command access is disabled.
Asserted when remote command access is enabled.
Asserted when a password entry fails while accessing a password protected
level of the L30.
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
Reset command is operated (set by all three operands below).
Communications source of the reset command.
Operand (assigned in the
of the reset command.
Reset key (pushbutton) source of the reset command.
Any of the major self-test errors generated (major error)
Any of the minor self-test errors generated (minor error)
Any self-test errors generated (generic, any error)
See description in Chapter 7: Commands and targets
See description in Chapter 7: Commands and targets
See description in Chapter 7: Commands and targets
See description in Chapter 7: Commands and targets
See description in Chapter 7: Commands and targets
See description in Chapter 7: Commands and targets
See description in Chapter 7: Commands and targets
See description in Chapter 7: Commands and targets
See description in Chapter 7: Commands and targets
See description in Chapter 7: Commands and targets
See description in Chapter 7: Commands and targets
See description in Chapter 7: Commands and targets
See description in Chapter 7: Commands and targets
See description in Chapter 7: Commands and targets
See description in Chapter 7: Commands and targets
See description in Chapter 7: Commands and targets
See description in Chapter 7: Commands and targets
See description in Chapter 7: Commands and targets
See description in Chapter 7: Commands and targets
See description in Chapter 7: Commands and targets
See description in Chapter 7: Commands and targets
See description in Chapter 7: Commands and targets
See description in Chapter 7: Commands and targets
See description in Chapter 7: Commands and targets
Asserted while the ambient temperature is greater than the maximum
operating temperature (80°C)